Plan Review Notes
Plan Review Notes For Permit 07080132
Permit Number 07080132
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-06 14:57:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST, NOT ADDRESSED:
  
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 _XX_ 7.)PROVIDE INFORMATION IN REGARDS TO THE
 SURROUNDING TERRAIN AND DECLARE EXPOSURE CATEGORY
 FBC1609.6.2.1(2), FBC R301.2.1.4.NOTE THAT THE
 DEFINITION FOR EXPOSURE C HAS CHANGED EFFECTIVE
 DECEMBER 8, 2006 FBC1609.4, FBC R301.2.1.4.
  
 NOTE THAT I CALLED CONTRACTOR AFTER FIRST REVIEW AND
 ASKED IF HE UNDERSTOOD THE ISSUES OF EXPOSURE CATEGORY
 AND ENHANCED FASTENING.CONTRACTOR INDICATED THAT HE
 DID UNDERSTAND AND DID NOT NEED ASSISTANCE.DECLARE
 THIS JOB AS EXPOSURE B OR EXPOSURE C AND PROVIDE
 INFORMATION IN REGARDS TO SURROUNDING AREA.THIS MAY
 BE DONE WITH AERIALS WHICH MAY BE AVAILABLE AT
 WWW.PBCGOV.COM/PAPA.THIS WILL BE REQUIRED TO
 DETERMINE DESIGN PRESSURES AND ENHANCED FASTENING.
  
 ALL COMMENTS MUST BE ADDRESSED PRIOR TO PERMIT
 ISSUANCE.
  
  
  