Plan Review Notes For Permit 07080102 |
Permit Number |
07080102 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-09 11:14:52 | | | | | THIS REVIEW WAS WAS MADE UNDER THE FOLLOWING CODES: THE | | 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH | | THE FOLLOWING: | | | | 1} THE PLANS ARE NOT DRAWN WITH ENOUGH CLARITY FOR | | REVIEW OR RECORD RETENTION. PLEASE INCREASE THE SIZE OF | | THE PLANS. | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | 106.3.4.3.FBC. | | | | 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND | | 106.3.5.4(8) FBC. | | 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION EVERY | | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY | | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC | | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | DISTINGUISHED FROM ALL OTHERS. INCLUDE OCP AND | | CONDUCTOR SIZES SO COMPLIANCE WITH 310.16 CAN BE | | REVIEWED. | | | | 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS. | | | | 5} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B). | | | | NOTE: RECEPTACLE SPACING MUST COMPLY WITH 210.52, 2005 | | NEC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|