Plan Review Notes
Plan Review Notes For Permit 07080102
Permit Number 07080102
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-09 11:14:52 
  
 THIS REVIEW WAS WAS MADE UNDER THE FOLLOWING CODES: THE
 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} THE PLANS ARE NOT DRAWN WITH ENOUGH CLARITY FOR
 REVIEW OR RECORD RETENTION. PLEASE INCREASE THE SIZE OF
 THE PLANS.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.3.4.3.FBC.
  
 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.
 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. INCLUDE OCP AND
 CONDUCTOR SIZES SO COMPLIANCE WITH 310.16 CAN BE
 REVIEWED.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS.
  
 5} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B).
  
 NOTE: RECEPTACLE SPACING MUST COMPLY WITH 210.52, 2005
 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  