Plan Review Notes
Plan Review Notes For Permit 07080077
Permit Number 07080077
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-05 16:45:00** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 PLEASE ALSO SEE THERE ARE NEW COMMENTS DUE TO CHANGES
 MADE ON PLANS AND INFORMATION NOW SUBMITTED WHICH WAS
 NOT ON PREVIOUSLY REVIEWED PLANS.
  
 1) NOTE: PLEASE SEE THE PLANS ARE NOW SIGNED, DATED AND
 SEALED BY AN ENGINEER HOWEVER THE PLANS DO NOT INDICATE
 ANY TITLE BLOCKS AS REQUIRED PER FAC 61G15-23.002, FS
 471.023
  
 2) NOTE: PLEASE SEE THE RISER NOW CONTAINS NOTES FOR
 THE EXISTING SERVICE WITH SOME ITEMS BEING NEW OR
 NEEDING TO MEET MINIMUM CODE FOR SAFETY.
 PLEASE SEE SOME ITEMS ARE NOT POSSIBLE AS SHOWN. PLEASE
 SEE THE BELOW FOR SOME EXAMPLES.
 RISER CONTAINS A NOTE #2 FOR CONDUCTORS FROM GUTTER TO
 MAIN DISCONNECT WHICH READS THE CONDUCTORS MUST BE
 SIZED FOR 400AMPS. HOW IS THIS POSSIBLE WHEN THE MAIN
 IS 600AMP RATED?
 RISER ALSO CONTAINS A NOTE #1 AS LISTED ON NOTES ON
 UPPER LEFT HAND CORNER OF PLANS WHICH STATES CONDUCTORS
 ARE TO BE RATED FOR 200AMPS. HOW IS THIS POSSIBLE WHEN
 THIS SAME MAIN IS 600AMPS AND THE CONDUCTORS ON HDP FOR
 FEEDERS IS THAT OF TWO SETS OF 350MCM.
 PLEASE ALSO SEE NOTE #1 FOR CONDUCTORS FROM TRANSFORMER
 TO LDP WHICH STATES CONDUCTORS ARE TO BE RATED FOR
 200AMPS! HOW IS THIS POSSIBLE WHEN THE MINIMUM RATING
 OF CONDUCTORS SHALL BE 400AMPS? THE RESPONSE MENTIONS
 THAT TWO CONDUITS ARE PRESENT AND IT IS BEING ASSUMED
 THAT THESE CONTAIN 3/0S. THE LDP PANEL STATES THE
 FEEDERS ARE 500 MCM. IN EITHER CASE THE CONDUCTORS
 WHICH ARE SHOWN ARE NOT RATED PER 310.16, 240.21.
 ** PLEASE CORRELATE NOTES AS THE AMPERAGES DO NOT
 CORRELATE WITH THE MINIMUM SIZES FOR LIFE SAFETY AND
 FIRE HAZARD.
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]