Plan Review Notes
Plan Review Notes For Permit 07080077
Permit Number 07080077
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-25 16:23:52*****DENIED*****
  
  
 1.PLEASE BE ADVISED THAT THE OCCUPANCY IS LOCATED IN
 THE JURISDICTION OF WEST PALM BEACH, NOT PALM BEACH AS
 INDICATED ON THE COVER SHEET (TA1.1) OR IN THE TITLE
 BLOCK OF THE SUBMITTED PLAN SHEETS.
  
 2.THE ACTUAL LOCATION OF THE PROJECTED SCOPE OF WORK,
 INCLUDING THE SUITE NUMBER AND THE TOWER (EAST OR WEST)
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.ON SHEET A2.1 UNDER THE DINING UPGRADE NOTES,
 REFERENCES ARE MADE TO SEE SHEET A1.3;HOWEVER THERE
 IS NO SUCH SHEET AS PER YOUR DRAWING INDEX OR INCLUDED
 IN THE PLAN.
  
 5.NO EXIT LIGHTS, EMERGENCY LIGHTS SHOWN ON SHEET
 A1.1, A2.1, OR E1.1.
  
 6.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 TO BE INSTALLED IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
 7.DETAIL THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFIES THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722