Plan Review Notes For Permit 07080077 |
Permit Number |
07080077 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-25 16:23:52 | *****DENIED***** | | | | | | 1.PLEASE BE ADVISED THAT THE OCCUPANCY IS LOCATED IN | | THE JURISDICTION OF WEST PALM BEACH, NOT PALM BEACH AS | | INDICATED ON THE COVER SHEET (TA1.1) OR IN THE TITLE | | BLOCK OF THE SUBMITTED PLAN SHEETS. | | | | 2.THE ACTUAL LOCATION OF THE PROJECTED SCOPE OF WORK, | | INCLUDING THE SUITE NUMBER AND THE TOWER (EAST OR WEST) | | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | SHEET. | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 4.ON SHEET A2.1 UNDER THE DINING UPGRADE NOTES, | | REFERENCES ARE MADE TO SEE SHEET A1.3;HOWEVER THERE | | IS NO SUCH SHEET AS PER YOUR DRAWING INDEX OR INCLUDED | | IN THE PLAN. | | | | 5.NO EXIT LIGHTS, EMERGENCY LIGHTS SHOWN ON SHEET | | A1.1, A2.1, OR E1.1. | | | | 6.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS | | TO BE INSTALLED IN TERMS OF CLASS A, CLASS B, OR CLASS | | C. | | | | 7.DETAIL THE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHERS WHICH SATISFIES THE 75' TRAVEL DISTANCE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|