2007-08-29 17:53:39 | 2007-08-29 17:53:39 |
| |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** SOME OF THESE CODES ARE SHOWN ON THE ARCHITECTURAL |
| SHEETS HOWEVER SOME ARE NOTE. PLEASE BE SURE THE |
| RELEVANT CODES ARE ON ELECTRICAL SHEETS ALSO. |
| |
| 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE |
| REQUIRED MISSING INFORMATION AS STATED BY THE FLORIDA |
| ADMINISTRATIVE CODE 61G1-16.004. |
| PLEASE SEE MISSING PRINTED NAME, PRINTED FIRM LICENSE |
| NUMBER WHICH IS ALSO KNOW AS A CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| PLEASE SEE FLORIDA STATUTES 481.219 |
| ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| ANY OTHER TRADE. |
| |
| 3) NOTE: PLEASE SEE ALL THREE SETS OF PLANS SUBMITTED |
| IN FACT CONTAIN A *RUBBER-STAMP* FOR THE SIGNATURE OF |
| THE ARCHITECT. THIS IS NOT PERMITTED PER FAC |
| 61G1-16.003, FS 481.221. MUST CONTAIN AN *ORIGINAL |
| SIGNATURE AND DATE* WHEN SIGNING AND SEALING PLANS. ** |
| THIS COMMENT IS REQUIRED FOR ALL SHEETS AND FOR ALL |
| TRADES WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| REVIEWER(S). |
| |
| 4) NOTE: THE SCOPE OF WORK IS NOT COMPLETELY CLEAR AT |
| THIS TIME FOR THE ELECTRICAL SERVICE. |
| THE RISER CONTAINS A NOTE WHICH MENTIONS TO *PROVIDE |
| BID TO RE-USE EXISTING TRANSFORMER* WHICH LEADS TO THE |
| SERVICE SHOWN ON RISER BEING A NEW SERVICE TO THE |
| SPACE. |
| PLEASE KNOW BASED ON FS 471.003 THE SERVICE AS SHOWN |
| MAY NOT BE DESIGNED BY AN ARCHITECT AND IN FACT NEEDS |
| TO BE DONE BY A PE LICENSED UNDER FS 471 AND FAC |
| 61G15-23 |
| PLEASE ADJUST AND COMPLETE. PLEASE ALSO SEE COMMENTS |
| BELOW AS THE RISER SHOWN NEW OR EXISTING DOES NOT MEET |
| THE NEC FOR SOME MINIMUM REQUIREMENTS. SOME OF THESE |
| ARE MINIMUM FOR FIRE HAZARD AND LIFE SAFETY. |
| |
| 5) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER NEEDS TO BE |
| ON PLANS AND ALSO ON PERMIT APPLICATION. |
| THE PLANS WILL BE ROUTED TO OUR ADDRESSING REVIEW TO |
| CONFIRM. |
| PLEASE REVISE TITLE BLOCKS ONCE SUITE/UNIT IS DONE. FAC |
| 61G1-16.004, 61G15-23.002 |
| FBC 106.1.2 |
| |
| 6) NOTE: PLEASE SEE 408.36, 240.21 AS THE TAPPED |
| CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER |
| SHALL TERMINATE IN OVER CURRENT PROTECTION WHICH LIMITS |
| THE LOAD ON THE CONDUCTOR FOR ITS RATED AMPERAGE. |
| 310.16. |
| RISER INDICATES THIS PANEL AS A 400AMP MLO PANEL WHICH |
| DOES NOT MEET NEC. |
| PLEASE SEE THE CONDUCTORS AS SHOWN AS 500MCM DO NOT |
| MEET THE MINIMUM FOR CODE AS STATED ABOVE. |
| PLEASE REVISE AND MAKE CORRECTIONS. |
| ** IF THIS RISER AS SHOWN IN FACT EXISTS, THE RISER |
| WILL STILL NEED TO MEET MINIMUM CODE AS THESE ITEMS FOR |
| TAPPED CONDUCTORS, OVER CURRENT PROTECTION AND LACK OF |
| CORRECT GROUNDING IS NOT SAFE. |
| THIS INFORMATION HAS BEEN FORWARDED TO THE CHIEF |
| ELECTRICAL INSPECTOR FOR SITE VISIT. THIS OFFICE MAY |
| ALSO OBTAIN A SITE VISIT TO GO OVER SCOPE WITH PLANS AS |
| SHOWN ON ANY SPECIFIC ITEMS WHICH MAY PRESENTLY BE |
| UNSAFE AND NEED TO BE CORRECTED. |
| |
| 7) NOTE: PLEASE RISER IS MISSING ALL EQUIPMENT |
| GROUNDING CONDUCTORS AFTER THE FIRST MEANS OF |
| DISCONNECT INCLUDING ON THE LINE AND LOAD SIDE OF THE |
| TRANSFORMER. |
| 250.20, 250.30, 250.110, 250.122 ETC. |
| |
| 8) NOTE: PLEASE SUBMIT AND SHOW ALL AIC RATINGS FOR NEW |
| SERVICE EQUIPMENT. |
| 110.9 |
| FBC 106.1.2, 106.1.1, 106.3.5.1.2 |
| |
| 9) NOTE: PLEASE SEE THE PLANS MENTIONS IN THE KEYED |
| NOTES THAT THERE ARE LOCATIONS WHICH NEW RECEPTACLES |
| WILL BE INSTALLED YET I COULD NOT LOCATE THESE NEW |
| RECEPTACLES AND LOW VOLTAGE LOCATIONS ON PLANS? PLEASE |
| COMPLETE PLANS BY SHOWING THESE LOCATIONS, SUBMIT THE |
| PANEL SCHEDULE(S) FOR NEW CIRCUITS ETC FBC 106.3.5.1.2, |
| NEC 310.16, 240.4, 408.4 ETC |
| |
| 10) NOTE: PLEASE CLARIFY WHERE THE LIGHTING CONTROLS |
| FOR NEW LIGHTING PER 13-415.1.ABC.1.1, .1.2 OF THE FBC |
| ARE? |
| 13-101 |
| PLEASE GIVE THE LIGHTING POWER DENSITIES PER 13-415.2 |
| |
| 11) NOTE: PLEASE VERIFY WITH THE FLORIDA POWER AND |
| LIGHT (FPL) THE RISER AS SHOWN WHICH INDICATES THE CT |
| CAN ON THE LOAD SIDE OF THE SERVICE MAINS. |
| PLEASE SEE SERVICE STANDARDS WHERE THESE ARE REQUIRED. |
| ( LINE SIDE) |
| |
| 12) NOTE: PLEASE KNOW DUE TO COMMENT #3 AND #2 ABOVE |
| ONE SET OF THE PLANS ARE BEING RETAINED BY THIS |
| OFFICE. |
| |
| |
| |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |