Plan Review Notes
Plan Review Notes For Permit 07080077
Permit Number 07080077
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-29 17:53:392007-08-29 17:53:39
  
 ** DENIED **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THESE CODES ARE SHOWN ON THE ARCHITECTURAL
 SHEETS HOWEVER SOME ARE NOTE. PLEASE BE SURE THE
 RELEVANT CODES ARE ON ELECTRICAL SHEETS ALSO.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED MISSING INFORMATION AS STATED BY THE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004.
 PLEASE SEE MISSING PRINTED NAME, PRINTED FIRM LICENSE
 NUMBER WHICH IS ALSO KNOW AS A CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA STATUTES 481.219
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 3) NOTE: PLEASE SEE ALL THREE SETS OF PLANS SUBMITTED
 IN FACT CONTAIN A *RUBBER-STAMP* FOR THE SIGNATURE OF
 THE ARCHITECT. THIS IS NOT PERMITTED PER FAC
 61G1-16.003, FS 481.221. MUST CONTAIN AN *ORIGINAL
 SIGNATURE AND DATE* WHEN SIGNING AND SEALING PLANS. **
 THIS COMMENT IS REQUIRED FOR ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 REVIEWER(S).
  
 4) NOTE: THE SCOPE OF WORK IS NOT COMPLETELY CLEAR AT
 THIS TIME FOR THE ELECTRICAL SERVICE.
 THE RISER CONTAINS A NOTE WHICH MENTIONS TO *PROVIDE
 BID TO RE-USE EXISTING TRANSFORMER* WHICH LEADS TO THE
 SERVICE SHOWN ON RISER BEING A NEW SERVICE TO THE
 SPACE.
 PLEASE KNOW BASED ON FS 471.003 THE SERVICE AS SHOWN
 MAY NOT BE DESIGNED BY AN ARCHITECT AND IN FACT NEEDS
 TO BE DONE BY A PE LICENSED UNDER FS 471 AND FAC
 61G15-23
 PLEASE ADJUST AND COMPLETE. PLEASE ALSO SEE COMMENTS
 BELOW AS THE RISER SHOWN NEW OR EXISTING DOES NOT MEET
 THE NEC FOR SOME MINIMUM REQUIREMENTS. SOME OF THESE
 ARE MINIMUM FOR FIRE HAZARD AND LIFE SAFETY.
  
 5) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER NEEDS TO BE
 ON PLANS AND ALSO ON PERMIT APPLICATION.
 THE PLANS WILL BE ROUTED TO OUR ADDRESSING REVIEW TO
 CONFIRM.
 PLEASE REVISE TITLE BLOCKS ONCE SUITE/UNIT IS DONE. FAC
 61G1-16.004, 61G15-23.002
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE 408.36, 240.21 AS THE TAPPED
 CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER
 SHALL TERMINATE IN OVER CURRENT PROTECTION WHICH LIMITS
 THE LOAD ON THE CONDUCTOR FOR ITS RATED AMPERAGE.
 310.16.
 RISER INDICATES THIS PANEL AS A 400AMP MLO PANEL WHICH
 DOES NOT MEET NEC.
 PLEASE SEE THE CONDUCTORS AS SHOWN AS 500MCM DO NOT
 MEET THE MINIMUM FOR CODE AS STATED ABOVE.
 PLEASE REVISE AND MAKE CORRECTIONS.
 ** IF THIS RISER AS SHOWN IN FACT EXISTS, THE RISER
 WILL STILL NEED TO MEET MINIMUM CODE AS THESE ITEMS FOR
 TAPPED CONDUCTORS, OVER CURRENT PROTECTION AND LACK OF
 CORRECT GROUNDING IS NOT SAFE.
 THIS INFORMATION HAS BEEN FORWARDED TO THE CHIEF
 ELECTRICAL INSPECTOR FOR SITE VISIT. THIS OFFICE MAY
 ALSO OBTAIN A SITE VISIT TO GO OVER SCOPE WITH PLANS AS
 SHOWN ON ANY SPECIFIC ITEMS WHICH MAY PRESENTLY BE
 UNSAFE AND NEED TO BE CORRECTED.
  
 7) NOTE: PLEASE RISER IS MISSING ALL EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST MEANS OF
 DISCONNECT INCLUDING ON THE LINE AND LOAD SIDE OF THE
 TRANSFORMER.
 250.20, 250.30, 250.110, 250.122 ETC.
  
 8) NOTE: PLEASE SUBMIT AND SHOW ALL AIC RATINGS FOR NEW
 SERVICE EQUIPMENT.
 110.9
 FBC 106.1.2, 106.1.1, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE THE PLANS MENTIONS IN THE KEYED
 NOTES THAT THERE ARE LOCATIONS WHICH NEW RECEPTACLES
 WILL BE INSTALLED YET I COULD NOT LOCATE THESE NEW
 RECEPTACLES AND LOW VOLTAGE LOCATIONS ON PLANS? PLEASE
 COMPLETE PLANS BY SHOWING THESE LOCATIONS, SUBMIT THE
 PANEL SCHEDULE(S) FOR NEW CIRCUITS ETC FBC 106.3.5.1.2,
 NEC 310.16, 240.4, 408.4 ETC
  
 10) NOTE: PLEASE CLARIFY WHERE THE LIGHTING CONTROLS
 FOR NEW LIGHTING PER 13-415.1.ABC.1.1, .1.2 OF THE FBC
 ARE?
 13-101
 PLEASE GIVE THE LIGHTING POWER DENSITIES PER 13-415.2
  
 11) NOTE: PLEASE VERIFY WITH THE FLORIDA POWER AND
 LIGHT (FPL) THE RISER AS SHOWN WHICH INDICATES THE CT
 CAN ON THE LOAD SIDE OF THE SERVICE MAINS.
 PLEASE SEE SERVICE STANDARDS WHERE THESE ARE REQUIRED.
 ( LINE SIDE)
  
 12) NOTE: PLEASE KNOW DUE TO COMMENT #3 AND #2 ABOVE
 ONE SET OF THE PLANS ARE BEING RETAINED BY THIS
 OFFICE.
  
  
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]