Date |
Text |
2007-12-24 09:18:39 | |
| BUILDING PLAN REVIEW |
| PERMIT: 07010426 |
| ADD: 4619 GEORGIA AVE. |
| CONT: STONE IMAGE INC. |
| TEL: (561)547-1177 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 3RD -12/24/07 |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| **THE ADDRESS ON THE APPLICAION WAS CHANGED TO 4619 |
| GEORGIA AVE HOWEVER, THE PLANS STILL SHOW THE ADDRESS |
| AS ?604 BRADLEY STREET? CLARIFY.** |
| NOTE:THIS PROJECT WAS SUBMITTED PREVIOUSLY UNDER |
| APPLICATION #07010426 WITH THE ADDRESS AS 4619 GEORGIA |
| AVE. THE SAME PROJECT IS NOW SUBMITTED WITH A NEW |
| DIFFERENT APPLICATION #07080065 AND 604 BRADLEY ST AS |
| THE ADDRESS. PLEASE RECTIFY THIS SITUATION WITH THE |
| FRONT COUNTER WHEN RESUBMITTING. |
| 2)OK |
| 3) OK |
| 4) OK. |
| 5)OK |
| |
| **NEW** |
| **SEE NOTE (A) BELOW. |
| INDICATE ON THE DRAWINGS THE INTERIOR FINISHES OF THE |
| NEW STRUCTURE. TOILET AND BATHING ROOM FLOORS SHALL |
| HAVE A SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS |
| UPWARD ON TO THE WALLS AT LEAST 6 INCHES.WALL WITHIN |
| 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE THE SAME |
| TYPE OF SURFACES MENTION ABOVE. FBC1210. NOTE: DRYWALL |
| WITH PAINT IS NOT CONSIDERED A HARD SURFACE. INDICATE |
| THE TYPE OF FINISH IN THE BATHROOM FROM THE FINISH |
| FLOOR TO AT LEAST 4 FEET ABOVE. |
| |
| 6)OK |
| |
| **NEW** |
| **NO RESPONSE NOT ADDRESSED** |
| A)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| PROVIDE INFORMATION BASE ON INTERIOR FINISH |
| REQUIREMENTS BASED ON OCCUPANCY.INTERIOR WALL AND |
| CEILING FINISH SHALL HAVE A FLAME SPREAD INDEX NOT |
| GREATER THAN THAT SPECIFIED IN TABLE 803.5. |
| |
| B)OK, |
| C)OK |
| D)OK |
| |
| E)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY (SEE |
| POLICY) |
| |
| _XX___1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| |
| _OK__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: |
| MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF |
| EACH ROOF TYPE |
| |
| _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| |
| _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| |
| _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES. |
| |
| _XX_6.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected]. |