Date |
Text |
2007-09-17 11:03:26 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. THE ADDRESS ON THE APPLICATION AND PLANS, (604 |
| BRADLEY ST.), DOES NOT REFLECT THE ADDRESS FOR THE PCN |
| NUMBER AND ADDRESS ON OUR SYSTEM. PLEASE CLARIFY. |
| SECTION 105.3. (SEE ADDRESSING STOP DATED 01-17-2007 ON |
| PERMIT NUMBER 07010426). INDICATE THE CORRECT ADDRESS |
| ON THE APPLICATION AND ON THE PLANS. |
| |
| 2. PLEASE EXPLAIN WHY THERE ARE TWO PERMITS APPLIED FOR |
| THE SAME PROJECT. PLEASE SUBMIT A LETTER INDICATING |
| THAT THE PREVIOUS APPLICATION BE VOIDED OR CLOSED TO |
| AVOID CONFUSION IN THE FUTURE. (SEE PERMIT NUMBER |
| 07010426). |
| |
| 3. THE LANDSCAPE PLANS SEAL IS NOT APPROVED. SEE FAC |
| 61G1-16.002 & FS 481.2055. SEAL TO BE APPROX. 2" IN |
| DIAMETER. |
| |
| 4. THE SURVEY SHEET REQUIRES THE SIGNED SEAL TO BE |
| DATED WHEN THE SEAL AND SIGNATURE ARE AFFIXED TO THE |
| DOCUMENT. FS 472.025. ALSO SEE ELECTRICAL REVIEW |
| COMMENT #7CONCERNING STAMPED SIGNATURES WHICH ARE NOT |
| APPROVED. |
| |
| 5. SUBMIT A MINIMUM OF 2 SETS OF PLANS. LOOSE LANDSCAPE |
| AND SURVEY PLANS ARE NOT APPROVED. COMPLETE BOUND SETS |
| OF PLANS REQUIRED. SECTIONS 106.1 & 106.1.3. |
| |
| 6. SHT A-1 SANITARY PLUMBING RISER DIAGRAM. THE |
| DRINKING FOUNTAIN IS NOT SHOWN ON THE RISER DIAGRAM. |
| SECTION 301.3.--ONLY THE FIXTURES WITHIN THE TOILET |
| ROOM SHALL CONNECT TO THE WET- VENTED HORIZONTAL BRANCH |
| DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE |
| DOWNSTREAM OF THE WET VENT. THE MOP SINK AND DRINKING |
| FOUNTAIN SHALL CONNECT DOWNSTREAM OF THE TOILET ROOM |
| FIXTURES. SECTION 909.1 (SEE RED LINE EXAMPLE ON ONE |
| SET OF PLAN TO CORRECT VIOLATION).--SHOW ALL PIPE |
| SIZES ON SANT. RISER DIAGRAM. TABLES 709.1, 710.1(1) & |
| 710.1(2). |
| |
| 7.SHT A-1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR |
| W/C |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| ___FOR LAV |
| A. 11-4.19.2 CLEARANCES - 29" REQD. - 28" INDICATED |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| |
| 8. SHT A-1 DETAIL SHOWS THE W/C 1'6" "MIN" OFF THE WALL |
| TO THE CENTERLINE OF THE FIXTURE. THE 1'6" MEASUREMENT |
| IS AN ABSOLUTE MEASURMENT. PLEASE DELETE THE REFERENCE |
| TO "MINIMUM" . SECTION 11-3.1.--W/C AND LAV ARE TO |
| BE A MINIMUM OF 30" CENTERLINE OF FIXTURE TO CENTERLINE |
| OF FIXTURE, NOT 18" AS SHOWN ON THE DETAIL PLEASE |
| CORRECT DETAIL. SECTION 405.3.1 & FIGURE 504.3.1.-- |
| ACCESSIBLE LAVS SHALL BE A MINIMUM OF 15" OFF THE WALL |
| TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED IN THE |
| 30" OF THE 30"X48" CLEAR FLOOR SPACE. PLEASE INDICATE |
| ON DETAIL. SECTION 11-4.19.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |