Plan Review Notes
Plan Review Notes For Permit 07080065
Permit Number 07080065
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-17 11:03:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE ADDRESS ON THE APPLICATION AND PLANS, (604
 BRADLEY ST.), DOES NOT REFLECT THE ADDRESS FOR THE PCN
 NUMBER AND ADDRESS ON OUR SYSTEM. PLEASE CLARIFY.
 SECTION 105.3. (SEE ADDRESSING STOP DATED 01-17-2007 ON
 PERMIT NUMBER 07010426). INDICATE THE CORRECT ADDRESS
 ON THE APPLICATION AND ON THE PLANS.
  
 2. PLEASE EXPLAIN WHY THERE ARE TWO PERMITS APPLIED FOR
 THE SAME PROJECT. PLEASE SUBMIT A LETTER INDICATING
 THAT THE PREVIOUS APPLICATION BE VOIDED OR CLOSED TO
 AVOID CONFUSION IN THE FUTURE. (SEE PERMIT NUMBER
 07010426).
  
 3. THE LANDSCAPE PLANS SEAL IS NOT APPROVED. SEE FAC
 61G1-16.002 & FS 481.2055. SEAL TO BE APPROX. 2" IN
 DIAMETER.
  
 4. THE SURVEY SHEET REQUIRES THE SIGNED SEAL TO BE
 DATED WHEN THE SEAL AND SIGNATURE ARE AFFIXED TO THE
 DOCUMENT. FS 472.025. ALSO SEE ELECTRICAL REVIEW
 COMMENT #7CONCERNING STAMPED SIGNATURES WHICH ARE NOT
 APPROVED.
  
 5. SUBMIT A MINIMUM OF 2 SETS OF PLANS. LOOSE LANDSCAPE
 AND SURVEY PLANS ARE NOT APPROVED. COMPLETE BOUND SETS
 OF PLANS REQUIRED. SECTIONS 106.1 & 106.1.3.
  
 6. SHT A-1 SANITARY PLUMBING RISER DIAGRAM. THE
 DRINKING FOUNTAIN IS NOT SHOWN ON THE RISER DIAGRAM.
 SECTION 301.3.--ONLY THE FIXTURES WITHIN THE TOILET
 ROOM SHALL CONNECT TO THE WET- VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. THE MOP SINK AND DRINKING
 FOUNTAIN SHALL CONNECT DOWNSTREAM OF THE TOILET ROOM
 FIXTURES. SECTION 909.1 (SEE RED LINE EXAMPLE ON ONE
 SET OF PLAN TO CORRECT VIOLATION).--SHOW ALL PIPE
 SIZES ON SANT. RISER DIAGRAM. TABLES 709.1, 710.1(1) &
 710.1(2).
  
 7.SHT A-1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___FOR LAV
 A. 11-4.19.2 CLEARANCES - 29" REQD. - 28" INDICATED
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 8. SHT A-1 DETAIL SHOWS THE W/C 1'6" "MIN" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. THE 1'6" MEASUREMENT
 IS AN ABSOLUTE MEASURMENT. PLEASE DELETE THE REFERENCE
 TO "MINIMUM" . SECTION 11-3.1.--W/C AND LAV ARE TO
 BE A MINIMUM OF 30" CENTERLINE OF FIXTURE TO CENTERLINE
 OF FIXTURE, NOT 18" AS SHOWN ON THE DETAIL PLEASE
 CORRECT DETAIL. SECTION 405.3.1 & FIGURE 504.3.1.--
 ACCESSIBLE LAVS SHALL BE A MINIMUM OF 15" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED IN THE
 30" OF THE 30"X48" CLEAR FLOOR SPACE. PLEASE INDICATE
 ON DETAIL. SECTION 11-4.19.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved