2007-09-02 10:37:46REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THIS SCOPE OF WORK WAS PREVIOUSLY APPLIED FOR UNDER
 PERMIT # 07010426. WHY HAS IT BEEN REAPPLIED UNDER A
 NEW PERMIT APPLICATION? THIS SHOULD EITHER BE
 RESUBMITTED UNDER THE PREVIOUS APPLICATION OR THE
 PREVIOUS APPLICATIN SHOULD BE VOIDED. PLEASE
 COMMUNICATE THE INTENTIONS TO THIS OFFICE SO THE PROPER
 STEPS IN PROCEEDING MAY BE DETERMINED.
  
 2. SHOW RATE OF MECHANICAL VENTILATION FOR TOILET ROOM
 IN ACCORDANCE WITH FBC,M TABLE 403.3.
  
 3. SHOW MEANS OF SUPPLY AIR OR MAKE-UP AIR FOR THE
 EXHAUST FAN PER FBC,M 403.1.
  
 4. SHOW LOCATION OF EXHAUST OUTLET AND OUTDOOR AIR
 INTAKE WHICH ARE BOTH TO BE IN COMPLIANCE WITH FBC,M
 401.5 AND 401.6.
  
 5. PROVIDE EQUIPMENT SCHEDULE FOR EXHAUST FAN TO BE
 INSTALLED AND SHOW SIZE OF EXHAUST DUCT TO BE USED PER
 FBC 106.3.5.1.4.
  
 6. A MECHANICAL PERMIT IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: