Date |
Text |
2007-08-29 19:00:31 | ** DENIED ** |
| |
| 1) NOTE: PLEASE SEE TWO REVIEWS WERE DONE UNDER PERMIT |
| NUMBER 07010426 WHICH IS STILL AN ACTIVE PERMIT. IT IS |
| COMPLETELY UNCLEAR WHY A NEW PERMIT APPLICATION FOR THE |
| SAME SCOPE OF WORK IS BEING SUBMITTED WHEN THE OTHER |
| PERMIT APPLICATION IS STILL ACTIVE. |
| |
| ** PLEASE SEE SOME COMMENTS FROM THE REVIEWS DONE UNDER |
| THE PERMIT # ABOVE IS STILL IN NEED OF ADDRESSING. |
| |
| 2) NOTE: PLEASE COMPLETE RISER WITH ALL FEEDERS AND |
| GROUNDING CONDUCTORS TO THE DETACHED STRUCTURE. |
| 310.16,240.4,215.5, ETC. |
| |
| 3) NOTE: PLEASE SEE MISSING THE REQUIRED GROUNDING |
| ELECTRODE SYSTEM AT THE DETACHED STRUCTURE PER 250.32, |
| 250.50. |
| |
| 4) NOTE: PLEASE SEE THE MISSING OVER CURRENT PROTECTION |
| IN THE EXISTING 150AMP RATED PANEL WHICH IS FEEDING THE |
| NEW SUB PANEL. |
| THERE ARE TOO MANY SECTIONS TO NOTE WHICH REQUIRES |
| THIS. |
| NEC 2005. |
| |
| 5) NOTE: PLEASE SEE THE PANELS DO NOT SUPPLY THE |
| INFORMATION NEEDED FOR REVIEW OF LOADS, EXISTING AND |
| NEW, THE CONDUCTORS ETC WHICH IS NOT COMPLETE. |
| FBC 106.3.5.1.2 |
| NEC 215.5,240.4,310.16,2 |
| |
| 6) NOTE: PLEASE SEE ONLY ONE SET OF PLANS FOR ALL ITEMS |
| WAS SUBMITTED. |
| ONLY ONE SURVEY, |
| ONLY ONE PLAN, |
| ONLY ONE LANDSCAPE PLAN. |
| PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS AS REQUIRED |
| PER FBC 106.1.1, 106.1.2 |
| |
| 7) NOTE: PLEASE SEE THE SIGNATURE ON THE SURVEY IS A |
| *RUBBER-STAMP* WHICH IS NOT PERMITTED PER FS 472.025. |
| MUST BE AN ORIGINAL SIGNATURE. |
| ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| ANY OTHER TRADE. |
| |
| 8) NOTE: PLEASE SEE THE SEAL ON THE LANDSCAPE ARCHITECT |
| PLANS IS NOT VALID UNDER THE REQUIREMENTS FROM THE |
| STATE AND FLORIDA ADMINISTRATIVE CODE, FAC 61G1-16.002. |
| (2INCH MIN SEAL). |
| ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| ANY OTHER TRADE. |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |