Plan Review Notes
Plan Review Notes For Permit 07080061
Permit Number 07080061
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-29 09:56:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PRESSURES ARE TOO LOW FOR EXPOSURE C.SEE OPENING
 1.AN OPENING OF 56X57, APPROX 22 SF, REQUIRES -36.7
 WITH A COEFFICIENT OF 1.21 FOR EXPOSURE C DECLARED;;
 FBC TABLE R301.2(2) AND (3), NEGATIVE PRESSURE SHOULD
 BE -44.4.YOU ARE DESIGNING TO A PRESSURE OF -40.4.
 THIS COMMENT APPLIES TO ALL OPENINGS.ANCHOR SCHEDULE
 MAY NEED TO BE REVISED.
  
 2.)SEE OPENING 2.YOU HAVE CIRCLED 37.1 ALONG WITH
 ANCHOR SPACING FOR THIS DESIGN PRESSURE.YOUR DECLARED
 DESIGN PRESSURE IS -40.9.YOU HAVE STATED THAT THE
 CHART IS FOR POSITIVE PRESSURES, BUT THIS IS NOT
 CORRECT.THE CHART IS FOR BOTH POSITIVE AND NEGATIVE
 PRESSURES.USE THE ROW FOR 47 ANCHORING.CHECK ALL
 OPENINGS AS THIS COMMENT MAY APPLY TO OTHER OPENINGS AS
 WELL.
  
 PLEASE HAVE THE QUALIFIER CONTACT ME TO SCHEDULE A
 MEETING REGARDING THE DESIGN PRESSURE ISSUE.