2008-06-03 12:12:15 | ** DENIED REVIEW FOR REVISIONS ** |
| |
| |
| ** PLEASE REVISE AND COORDINATE REVISIONS MADE TO |
| PLANS. |
| |
| 1) NOTE: PLEASE SEE THERE ARE ITEMS NOW OFF AND MISSING |
| FROM THE PLANS WHICH WERE LOCATED ON PREVIOUS PLANS |
| WHICH ARE JUST NO LONGER ON PLANS. |
| FOR EXAMPLE: |
| PLEASE SEE DRIVE SIGNS WHICH USED TO BE CIRCUIT L-30. |
| PLEASE SEE SOFFIT NEON WHICH USED TO BE ON PLANS ON |
| EAST SIDE OF BUILDING ALSO. |
| THESE ARE A COUPLE OF EXAMPLES WHICH COORDINATION IS |
| NEEDED. THIS MAY NOT BE AN EXHAUSTED LIST. |
| FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND |
| ADDITIONAL INFORMATION. |
| NEC 408.4 |
| |
| 2) NOTE: PLEASE SEE THE PLANS HAVE HAD SEVERAL REVISED |
| CIRCUITS FOR LIGHTING ETC YET THE SCHEDULE ON E-300 HAS |
| NOT BEEN REVISED. |
| FBC 106.1.2, NEC 408.4 |
| 13-415.1.ABC.1.1, 13-413.1.ABC.2.1, .2.2. |
| |
| 3) NOTE: PLEASE KNOW THE LOCK-OFF DEVICE WHICH IS SHOWN |
| FOR CIRCUIT L12 FOR EMERGENCY LIGHTS/EXIT LIGHTS SHALL |
| BE AN INTEGRAL PART OF THE BREAKER. MAY NOT BE OF A |
| SNAP ON/CLIP ON TYPE. THIS WILL BE FIELD VERIFIED. THIS |
| IS BEING SHOWN AS AN EXCEPTION TO 700.12E WHICH |
| REQUIRES ALL EMERGENCY LIGHTS AND EXIT LIGHTS TO BE |
| CIRCUITED TO LOCAL BRANCH CIRCUIT. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |