Plan Review Notes
Plan Review Notes For Permit 07080049
Permit Number 07080049
Review Stop E
Sequence Number 4
Notes
Date Text
2008-06-03 12:12:15** DENIED REVIEW FOR REVISIONS **
  
  
 ** PLEASE REVISE AND COORDINATE REVISIONS MADE TO
 PLANS.
  
 1) NOTE: PLEASE SEE THERE ARE ITEMS NOW OFF AND MISSING
 FROM THE PLANS WHICH WERE LOCATED ON PREVIOUS PLANS
 WHICH ARE JUST NO LONGER ON PLANS.
 FOR EXAMPLE:
 PLEASE SEE DRIVE SIGNS WHICH USED TO BE CIRCUIT L-30.
 PLEASE SEE SOFFIT NEON WHICH USED TO BE ON PLANS ON
 EAST SIDE OF BUILDING ALSO.
 THESE ARE A COUPLE OF EXAMPLES WHICH COORDINATION IS
 NEEDED. THIS MAY NOT BE AN EXHAUSTED LIST.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
 NEC 408.4
  
 2) NOTE: PLEASE SEE THE PLANS HAVE HAD SEVERAL REVISED
 CIRCUITS FOR LIGHTING ETC YET THE SCHEDULE ON E-300 HAS
 NOT BEEN REVISED.
 FBC 106.1.2, NEC 408.4
 13-415.1.ABC.1.1, 13-413.1.ABC.2.1, .2.2.
  
 3) NOTE: PLEASE KNOW THE LOCK-OFF DEVICE WHICH IS SHOWN
 FOR CIRCUIT L12 FOR EMERGENCY LIGHTS/EXIT LIGHTS SHALL
 BE AN INTEGRAL PART OF THE BREAKER. MAY NOT BE OF A
 SNAP ON/CLIP ON TYPE. THIS WILL BE FIELD VERIFIED. THIS
 IS BEING SHOWN AS AN EXCEPTION TO 700.12E WHICH
 REQUIRES ALL EMERGENCY LIGHTS AND EXIT LIGHTS TO BE
 CIRCUITED TO LOCAL BRANCH CIRCUIT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]