Plan Review Notes
Plan Review Notes For Permit 07080049
Permit Number 07080049
Review Stop M
Sequence Number 3
Notes
Date Text
2008-04-29 16:55:27REVIEW #: REVISION 2
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE DESIGN OF THE NEW DUCTWORK IN THE SHOWROOM IS
 UNCLEAR. IT LOOKS AS IF IT MAY BE SOME TYPE OF
 DUCT-SOCK SYSTEM, BUT IT IS NOT IDENTIFIED ON THE
 PLANS. PLEASE CLARIFY. FBCM 603.1, FBCB 106.1.1
  
 2. IF A DUCT SOCK TYPE SYSTEM IS USED, PLEASE PROVIDE
 SUBMITTAL DATA SHOWING WHICH TYPE OF SYSTEM IS TO BE
 USED AS WELL AS LISTING AND TESTING DATA. NONMETALLIC
 DUCTS SHALL BE CONSTRUCTED WITH CLASS 0 OR CLASS 1 DUCT
 MATERIAL IN ACCORDANCE WITH UL 181 PER FBCM 603.4.
  
 3. PLEASE SEE PROVISO FROM PREVIOUS PLAN REVIEW. ALL
 PROVISO ITEMS ARE TO BE ADDRESSED IN REVISION PRIOR TO
 INSPECTION. THIS WAS A CONDITION OF PERMIT AND HAS NOT
 BEEN ADDRESSED.
  