Plan Review Notes For Permit 07080049 |
Permit Number |
07080049 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-04-29 16:55:27 | REVIEW #: REVISION 2 | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. THE DESIGN OF THE NEW DUCTWORK IN THE SHOWROOM IS | | UNCLEAR. IT LOOKS AS IF IT MAY BE SOME TYPE OF | | DUCT-SOCK SYSTEM, BUT IT IS NOT IDENTIFIED ON THE | | PLANS. PLEASE CLARIFY. FBCM 603.1, FBCB 106.1.1 | | | | 2. IF A DUCT SOCK TYPE SYSTEM IS USED, PLEASE PROVIDE | | SUBMITTAL DATA SHOWING WHICH TYPE OF SYSTEM IS TO BE | | USED AS WELL AS LISTING AND TESTING DATA. NONMETALLIC | | DUCTS SHALL BE CONSTRUCTED WITH CLASS 0 OR CLASS 1 DUCT | | MATERIAL IN ACCORDANCE WITH UL 181 PER FBCM 603.4. | | | | 3. PLEASE SEE PROVISO FROM PREVIOUS PLAN REVIEW. ALL | | PROVISO ITEMS ARE TO BE ADDRESSED IN REVISION PRIOR TO | | INSPECTION. THIS WAS A CONDITION OF PERMIT AND HAS NOT | | BEEN ADDRESSED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|