Plan Review Notes For Permit 07080049 |
Permit Number |
07080049 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-11-24 15:49:09 | *****************PROVISO****************** | | 1. FLOAT SWITCH FOR RTU'S TO BE INSTALLED INTERNALLY ON | | PRIMARY DRAIN PAN, NOT INLINE ON PRIMARY CONDENSATE | | LINE, IN ACCORDANCE WITH FBC,M 307.2.3(2). | | | | 2. PROVIDE DETAIL FOR CONDENSING UNIT ATTACHMENT AS | | WELL AS ADDITIONAL SUPPORTS TO BE INSTALLED AS CALLED | | FOR BY NOTE ON M-200. SHOW COMPLIANCE WITH FBC,M 301.13 | | AND FBC CH.16. | | NOTE:REVIES PLANS ACCORDINGLY TO SHOW COMPLIANCE WITH | | THESE PROVISOS PRIOR TO INSPECTION. | | | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|