2007-11-09 12:54:51** DENIED **
  
  
 1) NOTE:PLEASE SEE THE LIGHTING POWER CALCULATIONS
 FOR DESIGN AND ALLOWANCES ARE DIFFERENT ON ELECTRICAL
 PLANS ON SHEET E-300 THAN ON THE METHOD *C* AS
 SUBMITTED ALONG WITH SUBMITTALS.
 PLEASE SEE 13-415.2 AND COORDINATE PLANS/CALCULATIONS.
 FOR EXAMPLE: MAXIMUM LIGHTING POWER ALLOWANCE AS LISTED
 ON SHEET METHOD *C* IS SHOWN AS 7,983, YET TABLE
 CALCULATIONS ON SHEET E-300 SHOWS DESIGN AT 11,397.
 THIS EXCEEDS THE MAXIMUM AS STATED ON FORM 400C-04.
  
 THE LPD ON THE TABLES DOE HOWEVER SHOW A DESIGN LESS
 THAN THE ALLOWANCE ON THIS SAME SHEET.
 PLEASE EXPLAIN AND COORDINATE THESE DIFFERENCES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  