2007-11-21 09:49:17 | ****CORRECTIONS**** |
| |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)PLEASE INCLUDE A RESPONSE LETTER.THIS HELPS TO |
| EXPEDITE PLAN REVIEW. |
| |
| 2.)NOC; REQUIRED BY FS713.13. |
| |
| 3.)PLANS WILL BE REDLINED TO INCUDE 2007 AMENDMENTS |
| IF AGREED BY ARCHITECT. |
| |
| 4.)ADDRESSED. |
| |
| 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| FAC9B72. |
| |
| 5A.I HAVE PRINTED YKK DOOR PRODUCT APPROVAL FOR YOU. |
| PLEASE SEE THE NOTE AT THE BOTTOM OF THE PRODUCT |
| APPROVAL.THE DESIGN PRESSURES ARE TO BE REDUCED BY |
| DIVIDING BY 1.33 OR BY BEING CERTIFIED BY AN ENGINEER. |
| SEE SHEET 3.NOT ALL OF THE GLASS OPTIONS ARE |
| COMPLIANT WITH THE DESIGN PRESSURE REQUIREMENT OF -55.3 |
| FOR THE 3'0' X 8'0' DOOR WHEN DIVIDED BY 1.33.PLEASE |
| CIRCLE WHICH GLASS OPTION YOU ARE USING. |
| |
| 5F.PRODUCT APPROVAL FOR THE ROOF HATCH CAN BE A |
| PROVISO ITEM AS STATED IN THE PREVIOUS LIST.A CO HOLD |
| HAS BEEN PLACED ON THIS PERMIT SUBJECT TO THIS |
| REQUIREMENT.PLEASE NOTE THAT THE PLAN SPECIFIES A |
| BILCO ROOF HATCH, BUT THE PRODUCT APPROVAL PACKAGE |
| SUBMITTED REFERS TO NYSTROM BUILDNG PRODUCTS ROOF |
| HATCH. |
| |
| 6C.SHEET A103 HAS SEVERAL COUNTER AREAS, RETAIL PARTS |
| BOUTIQUE, SERVICE TECH AREA AND CASHIERS STATION. |
| PLEASE REVIEW REQUIREMENTS FOR SERVICE COUNTERS FOR |
| SALES OR DISTRIBUTION OF GOODS TO THE PUBLIC |
| FBC11-4.7.2 AND PROVIDE ELEVATIONS SHOWING COMPLIANCE. |
| |
| IT IS NOT CLEAR HOW THIS WAS ADDRESSED.NO ELEVATIONS |
| OR NOTES SHOWING CODE COMPLIANCE WERE PROVIDED. |
| |
| 7A)A ROOF PRODUCT APPROVAL WAS SUBMITTED, BUT THIS IS |
| FOR A WOOD DECK.SP1 STATES THAT THIS IS TYPE IIB, |
| NONCOMBUSTIBLE.PLEASE CORRELATE. |
| |
| 7B.)THE ROOF PRODUCT APPROVAL REFERS TO GENERAL |
| LIMITATION #9, NO ENHANCED FASTENING ALLOWED AND THE |
| APPROVED ASSEMBLIES LISTED ARE LIMITED TO -45PSF. |
| SPECIFY ROOF DESIGN PRESSURES AND SUBMIT PRODUCT |
| APPROVAL FOR THE CORRECT ROOF DECK TYPE AND WHICH MEETS |
| OR EXCEEDS THE DESIGN PRESSURES.AN APPROVED ASSEMBLY |
| WILL BE REQUIRED TO BE SELECTED ALONG WITH ENHANCED |
| FASTENING PATTERN WHEN APPLYING FOR THE ROOF PERMIT. |
| |
| |
| |
| |
| |
| |
| |
| |