Plan Review Notes
Plan Review Notes For Permit 07080049
Permit Number 07080049
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-17 08:58:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. INDICATED THE LEVEL OF ALTERATION PER SECTIONS 303,
 304 OR 305.
  
 2. SHT SP-1 OCCUPANCY LOAD. MINIMUM FACILITIES AS SHOWN
 ARE NOT CORRECT. THREE W/C'S AND 3 LAVS REQUIRED.
 PLEASE CORRECT MINIMUM FACILITIES SHOWN.
  
 3. MORE INFORMATION REQUIRED. PLEASE PROVIDE AN
 EXISTING FLOOR PLAN PRIOR TO ALTERATIONS TO DETERMINE
 THE EXTENT OF THE CHANGES TO THE FLOOR PLAN. SECTION
 106.1.2.
  
 4. PER SECTION 606.1 EXIST. BLDG. CODE, A BUILDING,
 FACILITY OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE. THE STALLS IN
 ROOMS A117 & A118 SHALL MEET THE REQUIREMENTS OF
 11-4.17.3 EXCEPTION NEW CONTRUCTION (1) & (2). A LAV IS
 REQUIRED IN THE STALL, AND THE W/C SHALL BE LOCATED IN
 THE CORNER DIAGONAL TO THE DOOR. PLEASE SHOW
 COMPLIANCE.
  
 5. SUBMIT A DETAIL & ELEVATION FOR THE TECH LUNCH ROOM
 SINK. SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS FOR THE SINK. FORWARD APPROACH IS REQUIRED
 AND THE CABINET DOORS ARE NOT ALLOWED IN THE CLEAR
 FLOOR SPACE.
  
 6. SHT P-100 ALL DEMO'D PIPING BEING CAPPED. IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. SECTION 704.5. INDICATED HOW THE
 CAPPING OF THE PIPING WILL COMPLY.
  
 7. SHT P-100 SANITARY RISER DIAGRAM. ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT.
 SECTION 909.1. THE SINK IN THE TECH LUNCH ROOM SHALL
 CONNECT DOWNSTREAM OF THE TOILET ROOM FIXTURES.
  
 8. A WATER RISER DIAGRAM FOR ALL NEW WORK IS REQUIRED
 PER SECTION 106.3.5.1.3(3)(10)(13). PLEASE SUBMIT A
 WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES AND
 WATER HAMMER ARRESTORS, (IF REQUIRED BY SECTION
 604.9).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved