Date |
Text |
2007-09-17 08:58:28 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 EXISTING BUILDING CODE |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. INDICATED THE LEVEL OF ALTERATION PER SECTIONS 303, |
| 304 OR 305. |
| |
| 2. SHT SP-1 OCCUPANCY LOAD. MINIMUM FACILITIES AS SHOWN |
| ARE NOT CORRECT. THREE W/C'S AND 3 LAVS REQUIRED. |
| PLEASE CORRECT MINIMUM FACILITIES SHOWN. |
| |
| 3. MORE INFORMATION REQUIRED. PLEASE PROVIDE AN |
| EXISTING FLOOR PLAN PRIOR TO ALTERATIONS TO DETERMINE |
| THE EXTENT OF THE CHANGES TO THE FLOOR PLAN. SECTION |
| 106.1.2. |
| |
| 4. PER SECTION 606.1 EXIST. BLDG. CODE, A BUILDING, |
| FACILITY OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH |
| CHAPTER 11 OF THE FLORIDA BUILDING CODE. THE STALLS IN |
| ROOMS A117 & A118 SHALL MEET THE REQUIREMENTS OF |
| 11-4.17.3 EXCEPTION NEW CONTRUCTION (1) & (2). A LAV IS |
| REQUIRED IN THE STALL, AND THE W/C SHALL BE LOCATED IN |
| THE CORNER DIAGONAL TO THE DOOR. PLEASE SHOW |
| COMPLIANCE. |
| |
| 5. SUBMIT A DETAIL & ELEVATION FOR THE TECH LUNCH ROOM |
| SINK. SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL |
| SUBSECTIONS FOR THE SINK. FORWARD APPROACH IS REQUIRED |
| AND THE CABINET DOORS ARE NOT ALLOWED IN THE CLEAR |
| FLOOR SPACE. |
| |
| 6. SHT P-100 ALL DEMO'D PIPING BEING CAPPED. IN THE |
| REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS |
| SHALL BE PROHIBITED. SECTION 704.5. INDICATED HOW THE |
| CAPPING OF THE PIPING WILL COMPLY. |
| |
| 7. SHT P-100 SANITARY RISER DIAGRAM. ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE |
| WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT. |
| SECTION 909.1. THE SINK IN THE TECH LUNCH ROOM SHALL |
| CONNECT DOWNSTREAM OF THE TOILET ROOM FIXTURES. |
| |
| 8. A WATER RISER DIAGRAM FOR ALL NEW WORK IS REQUIRED |
| PER SECTION 106.3.5.1.3(3)(10)(13). PLEASE SUBMIT A |
| WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES AND |
| WATER HAMMER ARRESTORS, (IF REQUIRED BY SECTION |
| 604.9). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |