Plan Review Notes
Plan Review Notes For Permit 07080049
Permit Number 07080049
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-22 16:02:14REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF FBC, EXISTING BUILDING.
 PLEASE INCLUDE THE LEVEL OF ALTERATION IN THE CODE
 SUMMARY SECTION OF PG SP-1.
  
 2.RENOVATED COMMERCIAL BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION 202 OF FBC CH.13), COMPLY WITH
 THE PRESCRIPTIVE REQUIREMENTS CONTAINED IN FORM 400C OR
 WITH METHOD B OF SUBCHAPTER 13-4 FOR INSULATION, HVAC
 SYSTEMS, LIGHTING, WATER HEATING SYSTEMS AND EXTERIOR
 ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED IN
 ACCORDANCE WITH FBC 13-101.1.3. PROVIDE ENERGY
 CALCULATIONS ON FORM 400B OR 400C SIGNED AND SEALED PER
 FBC 13-103.1.1.1.
  
 3. DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 4. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC,M 307.2.1 AND FBC 1503.6.
  
 5. SHOW MEANS OF AUXILIARY DRAIN PROTECTION FOR RTU'S
 PER FBC,M 307.2.3. A WATER LEVEL DETECTION DEVICE
 (FLOAT SWITCH) IN THE PRIMARY DRAIN PAN OF THE RTU'S
 WILL SATISFY THIS REQUIREMENT.
  
 6. PG M-400 VERTICAL AC DETAIL: THIS DETAIL SHOWS A
 FLOAT SWITCH ON THE SECONDARY DRAIN OUTLET. THE SUPPLY
 AIR UNIT SCHEDULE CALLS FOR AN AUXILIARY DRAIN PAN W/
 FLOAT SWITCH. PLEASE CLARIFY WHICH METHOD IS TO BE USED
 OR PROVIDE BOTH. FBC,M 307.2.3
  
 7. PROVIDE A COMPREHENSIVE AIR BALANCE SCHEDULE WHICH
 INCLUDES EXHAUST AIR TOTALS TO SHOW THE BUILDING TO BE
 PRESSURISED WITH RESPECT TO THE OUTDOORS PER FBC
 13-409.1.ABC.2.
  
 8. SHOW BY WHAT MEANS THE OUTDOOR AIR FOR AC-1 AND AC-2
 IS PROVIDED. OUTDOOR AIR INTAKES ARE TO BE LOCATED IN
 COMPLIANCE WITH FBC,M 401.5 AND 401.6.
  
 9. PG M-100: DUCTS FOR AC-1 AND AC-2 ARE SHOWN
 PENETRATING THE 2ND FLOOR SLAB. SHOW HOW THESE OPENINGS
 ARE TO BE PROTECTED IN ACCORDANCE WITH FBC,M 607.5.
  
 10. PG M-400 RTU DETAIL: THERE IS NO SUCH THING AS
 TABLE 1606.1.4 IN THE FLORIDA BUILDING CODE. PROVIDE
 COMPLETE DETAIL AND WIND LOAD CALCULATIONS SHOWING HOW
 ALL OUTDOOR EQUIPMENT (RTU'S AND CU'S) IS TO BE SECURED
 TO MEET WIND LOAD REQUIREMENTS PER FBC,M 301.13 AND FBC
 CH.16.
  