Date |
Text |
2007-08-25 18:56:30 | 2007-08-25 18:56:30 |
| |
| *** DENIED *** |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| 2) NOTE: PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER |
| 13. |
| PLANS INDICATE SEPARATE SPACE CONTROL FOR MOST AREAS, |
| HOWEVER PLEASE CLARIFY AREAS SUCH AS THE MANAGER'S |
| OFFICES,A108 AND SOME OTHER SEPARATE SPACES. |
| 13-415.1.ABC.1.2 |
| PLEASE SUBMIT INFORMATION FOR MAXIMUM TIMES FOR THE |
| OVER RIDE AND OCCUPANCY SENSOR TYPE DEVICES AS SHOWN ON |
| PLANS. THESE COULD NOT BE LOCATED ON THE SYMBOL LEGEND |
| AND INFORMATION THE TYPE OF THE DEVICES. PLEASE SEE THE |
| BATHROOMS ARE INDICATING A OC DEVICE WHICH IS OK, |
| HOWEVER PLEASE EXPAND ON THE TYPE OF DEVICE. WILL THIS |
| BE A COMBINATION DEVICE WHICH PROVIDES COVERAGE FOR |
| BLIND SPOTS , STALLS. (ULTRASONIC TYPE?) |
| PLEASE SUBMIT THE TIMED SCHEDULING INFORMATION. THE |
| PLANS INDICATE THE LIGHTING TO A TIME CLOCK HOWEVER NO |
| INFORMATION OR DETAIL FOR THIS WAS SUBMITTED OR COULD |
| BE LOCATED ON PLANS. |
| PLEASE PROVIDE OVER RIDE DEVICES, LOCATIONS AND TIMES |
| PER 13-415.1.ABC.1.1, .1.2. |
| PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO |
| ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA |
| COORDINATES WITH THE PLANS. |
| PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS |
| PER 13-415.2. |
| PLEASE SEE PLEASE KNOW AT THIS TIME NOT REVIEW FOR |
| LIGHTING COMPLIANCE CAN BE DONE FOR INTERIOR AND |
| EXTERIOR LIGHTING POWER ALLOWANCES. PLEASE SEE |
| 13-415.2, 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, |
| 13-415.2.ABC.1.1 |
| |
| 3) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF THE |
| EMERGENCY/EXIT LIGHTS. THE BRANCH CIRCUIT FEEDING THE |
| UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| AHEAD OF ANY LOCAL SWITCHES. PLEASE SHOW AND ADJUST |
| CIRCUITING. |
| |
| 4) NOTE: PLEASE IDENTIFY THE CIRCUITS ON THE PANEL |
| SCHEDULE AS NEW OR EXISTING. SOME OF THESE ARE ALREADY |
| DONE FOR THE NEW A/C EQUIPMENT. |
| PLEASE SEE THESE CAN BE SIMPLY DONE BY AN *E* OR *N* ON |
| THE BRANCH CIRCUITS ON PANEL SCHEDULE OR AN *ASTERISK* |
| WITH A NOTE AT THE BOTTOM OF PANEL SCHEDULE OR BY ANY |
| OTHER MEANS DECIDED BY THE DESIGN PROFESSIONAL. |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |