Plan Review Notes
Plan Review Notes For Permit 07080049
Permit Number 07080049
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-25 18:56:302007-08-25 18:56:30
  
 *** DENIED ***
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER
 13.
 PLANS INDICATE SEPARATE SPACE CONTROL FOR MOST AREAS,
 HOWEVER PLEASE CLARIFY AREAS SUCH AS THE MANAGER'S
 OFFICES,A108 AND SOME OTHER SEPARATE SPACES.
 13-415.1.ABC.1.2
 PLEASE SUBMIT INFORMATION FOR MAXIMUM TIMES FOR THE
 OVER RIDE AND OCCUPANCY SENSOR TYPE DEVICES AS SHOWN ON
 PLANS. THESE COULD NOT BE LOCATED ON THE SYMBOL LEGEND
 AND INFORMATION THE TYPE OF THE DEVICES. PLEASE SEE THE
 BATHROOMS ARE INDICATING A OC DEVICE WHICH IS OK,
 HOWEVER PLEASE EXPAND ON THE TYPE OF DEVICE. WILL THIS
 BE A COMBINATION DEVICE WHICH PROVIDES COVERAGE FOR
 BLIND SPOTS , STALLS. (ULTRASONIC TYPE?)
 PLEASE SUBMIT THE TIMED SCHEDULING INFORMATION. THE
 PLANS INDICATE THE LIGHTING TO A TIME CLOCK HOWEVER NO
 INFORMATION OR DETAIL FOR THIS WAS SUBMITTED OR COULD
 BE LOCATED ON PLANS.
 PLEASE PROVIDE OVER RIDE DEVICES, LOCATIONS AND TIMES
 PER 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA
 COORDINATES WITH THE PLANS.
 PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS
 PER 13-415.2.
 PLEASE SEE PLEASE KNOW AT THIS TIME NOT REVIEW FOR
 LIGHTING COMPLIANCE CAN BE DONE FOR INTERIOR AND
 EXTERIOR LIGHTING POWER ALLOWANCES. PLEASE SEE
 13-415.2, 13-415.2.ABC.1.2, 13-415.2.ABC.1.3,
 13-415.2.ABC.1.1
  
 3) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF THE
 EMERGENCY/EXIT LIGHTS. THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. PLEASE SHOW AND ADJUST
 CIRCUITING.
  
 4) NOTE: PLEASE IDENTIFY THE CIRCUITS ON THE PANEL
 SCHEDULE AS NEW OR EXISTING. SOME OF THESE ARE ALREADY
 DONE FOR THE NEW A/C EQUIPMENT.
 PLEASE SEE THESE CAN BE SIMPLY DONE BY AN *E* OR *N* ON
 THE BRANCH CIRCUITS ON PANEL SCHEDULE OR AN *ASTERISK*
 WITH A NOTE AT THE BOTTOM OF PANEL SCHEDULE OR BY ANY
 OTHER MEANS DECIDED BY THE DESIGN PROFESSIONAL.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved