2007-09-12 15:57:53BUILDING PLAN REVIEW
 SEPT. 10, 2007
 PERMIT: 07080049
 ADD: 2345 OKEECHOBEE BLVD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7131
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A) SHEET SP-1 CODE SUMMERY, THE PLANS FAIL TO INDICATE
 AS TO WHICH EDITION OF THE CODE THIS BUILDING IS BEING
 DESIGNED TO. 2004 FLORIDA BUILDING CODE W/ 2006
 AMENDMENTS.
  
 3B) THE PERMIT APPLICATION AND PLAN INDICATE THAT THE
 WORK TO BE COMPLETED UNDER THIS PERMIT IS A COMMERCIAL
 REMODEL. PLEASE SEE 2004 EXISTING BUILDING CODE-
 BUILDINGW/ 2006 AMENDMENTS. PLEASE INDICATE ON THE
 PLANS AS WELL AS THE LEVEL OF ALTERATIONS?
  
 4A) SHEET A-102 THERE IS 2 NEW COLUMNS ON COLUMN LINE
 A-2 & COLUMN LINE A-6 PLEASE PROVIDE A CUT SECTION
 THROUGH THIS AREA, PLAN ARE NOT CLEAR AS TO THE
 ANCHORING TO SLAB AND OR MAIN RESISTING SYSTEM FROM THE
 ROOF THROUGH TO THE FOUNDATION.
  
 4B) SHEET A-102 PLEASE PROVIDE A CUT SECTION THROUGH AT
 GRADE TO INDICATE HOW THE COMPONENTS WILL ENTER ACT AT
 GRADE OR IF SIDEWALK AT AIDE WALK.
 2603.9.2 CLEARANCE BETWEEN EARTH AND FOAM PLASTICS
 APPLIED TO THE EXTERIOR WALL SHALL BE NOT LESS THAN 6
 INCHES (152 MM).
  
 5A) SHEET A-102 INDICATES THAT THE EXISTING STOREFRONT
 WILL BE REUSED, BUT THE PRODUCT APPROVALS SUBMITTED
 HAVE ALUMIGLASS CURTAIN WALL SYSTEM AS PART OF THE
 PACKAGE.
 NOTE: THIS REPORT IF TO BE USED WILL NEED TO DIVIDE THE
 PRESSURES BY 1.33 FOR HAVE A FLORIDA LICENSED P.E.
 RESEARCH THE FASTENING SYSTEM. BEFORE THE 2004 FBC
 MANUFACTURES TOOK STEEL INCREASES OF 1.33% ON THE
 FASTENING SYSTEM.
  
 5B) SHEETS A-101 AND A-102 BOTH INDICATE THE USE OF
 EXTERIOR BI-FOLD DOORS, A 3?-0?
 WIDE EXTERIOR SWING DOOR AND A 6?-0? WIDE SWING DOOR.
 THE WERE NO PRODUCT APPROVALS SUBMITTED FOR THESE
 OPENINGS AT ALL. 1609.1.4.
  
 5C) THERE ARE NO DETAIL SHEETS HOW THE BI-FOLD DOORS
 AND SWING DOORS WERE TESTED AS AN ASSEMBLY, NOTE IS
 THERE A DOOR JAMB ON THE LATCH SIDE OF THE SWING DOOR,
 DOES THE BI-FOLD DOOR HAVE WHAT TYPE OF LOCKING
 ASSEMBLY THAT ALLOWS THE SWING DOOR TO LOCK INTO ITS
 RAILS? 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 5D) SUBMITTED ALSO ARE STORM SHUTTER PRODUCT APPROVALS
 BUT THERE IS NO KEY PLAN INDICATING TO WHICH OPENINGS
 THEY ARE TO BE PLACED? SHEET A-107 NOTE INDICATES NEW
 STOREFRONTS WITH BI-FOLD DOORS, ARE THE STOREFRONT
 WINDOWS GETTING REPLACED?
  
 5E)EASTERN METAL ALSO WILL REQUIRE A FLORIDA COVER
 SHEET.PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 5F) SHEET A-102 ALSO INDICATES THE USE OF A NEW ROOF
 HATCH. RULE 9B-72 REQUIRES A PRODUCT APPROVAL FOR SUCH
 ROOF OPENINGS. CURRENTLY THERE ARE NONE AVAILABLE BUT
 THERE ARE MANUFACTURERS CURRENTLY UNDERGOING TESTING
 AND CERTIFICATION THROUGH MIAMI-DADE TESTING PROGRAM.
 THIS ISSUE WILL BE A PROVISO:THAT IF THE MANUFACTURER
 DOES NOT ACQUIRE A ACCEPTANCE REPORT THROUGH THE STATE
 OR MIAMI-DADE THEN THE
 MANUFACTURER WILL BE REQUIRED TO SUBMIT TO THE CITY AND
 ACQUIRE A LOCAL PRODUCT APPROVAL BEFORE A CERTIFICATE
 OF COMPLETION WILL BE ISSUED. RULE 9B-72, 106.3.3.*
  
 6A) SHEET A-103 STAIR# A111 HAS A PASSAGEWAY TO THE
 EXTERIOR OF THE BUILDING,THIS STAIRWAY HAS 2 DOORS
 WHERE THE 18 ? IS MISSING ON THE PULL SIDE AT THE
 LATCH.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
  
 6B) SHEET A-103 SERVICE TECH ROOM# 119 PLEASE SEE DOORS
 IN SERIES: 11-4.13.7 TWO DOORS IN SERIES.THE MINIMUM
 SPACE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES
 SHALL BE 48 INCHES (1219 MM) PLUS THE WIDTH OF ANY DOOR
 SWINGING INTO THE SPACE. DOORS IN SERIES SHALL SWING
 EITHER IN THE SAME DIRECTION OR AWAY FROM THE SPACE
 BETWEEN THE DOORS [SEE FIGURE 26 (A)].
  
 6C) SHEET A-103 HAS SEVERAL COUNTER AREAS, RETAIL PARTS
 BOUTIQUE, SERVICE TECH AREA AND CASHIERS STATION. ALL
 SHOW VARIOUS DETAILS ON EITHER SHEET A-12 AND A-14.
 THESE SHEETS ARE NOT INCLUDED IN THESE PLANS OR
 INDEX.PLEASE REVIEW REQUIREMENTS FOR SERVICE COUNTERS
 FOR SALES OR DISTRIBUTION OF GOODS TO THE PUBLIC.
 11-4.7.2. PROVIDE ELEVATIONS SHOWING COMPLIANCE.
  
 6D) SHEET A-103 THE WOMEN?S RESTROOM A117 HAS 2 DOORS
 IN SERIES, 1A117B AND DOOR 2A117B THE SECOND DOOR DOES
 NOT INDICATE WHAT THE USAGE WILL BE? PLEASE REVIEW
 11-4.13.7 TWO DOORS IN SERIES.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTINGREPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROOF HATCH
 B) EFIS SYSTEMS
 C) ROOF ASSEMBLIES- WORK ON THE ROOF
  
 8)PLEASE MAKE CORRECTION AS TO WORK THAT WILL BE
 COMPLETED ON THE 2ND FLOOR IS RELATED TO A/C. PERMIT
 APPLICATION.
  
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  