2007-08-27 10:37:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SHUTTER CONNECTION MOUNTING TYPE APPEARS TO BE C2.
 YOU'VE STATED "A" ON THE INSTALLATION SCHEDULE, DETAIL
 A SHOWS C2, BUT YOU'VE CIRCLED C1.PLEASE KEEP ALL
 INFORMATION CONSISTENT.
  
 2.)OPENING 1 STATES YOU ARE USING DETAIL I.THIS
 DETAIL IS FOR A WOOD SUBSTRATE, THIS IS CONCRETE.
 PLEASE ADDRESS.
  