Plan Review Notes
Plan Review Notes For Permit 07071053
Permit Number 07071053
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-10 14:27:00 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUNDNONCOMPLIANT WITH THE
 FOLLOWING:
  
 SAME COMMENTS AS PREVIOUS REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES
 APPLY. AN IF ARCHITACTS TITLE BLOCK APPEARS ON THE
 PLAN, HE MUST SIGN AND SEAL, WET SIGNATURE, NOT A COPY.
  
 TO FURTHER EXPLAIN: IF THE ARCHITECTS TITLE BLOCK IS ON
 THE PLANS, HE MUST SIGN AND SEAL, THE PLANS BELONG TO
 HIM AS THE DESIGNER OF RECORD. YOU AS A CONTRACTOR
 CANNOT USE HIS DRAWINGS, AND ALTER THEM, WITHOUT HIM
 SIGNING OFF. SEE 481 F.S.
  
 2} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
 THE VALUE WAS NOT ADJUSTED OR FEES PAID ON THE CORRECT
 VALUE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]