Plan Review Notes
Plan Review Notes For Permit 07071047
Permit Number 07071047
Review Stop G
Sequence Number 1
Notes
Date Text
2007-08-13 14:06:11DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SEE ZONING REVIEW NOTE #1 AND ELECTRICAL REVIEW
 NOTE #3 IN REFERENCE TO THE PLACEMENT OF THE GENERATOR
 AND CORRELATE THE GAS ISOMETRIC IF NEEDED.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE ATTACHED PERMIT INFORMATION ATTACHED TO
 THE GAS REVIEW INDICATING NAT/GAS AT SAID ADDRESS.
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE ATTACHED PERMIT INFORMATION ATTACHED TO
 THE GAS REVIEW INDICATING NAT/GAS AT SAID ADDRESS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
  
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721