Plan Review Notes For Permit 07071047 |
Permit Number |
07071047 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-13 14:06:11 | DENIED | | REFERENCE: | | ** FBC-2004 FUEL GAS. | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | REQUIREMENTS. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE. | | ** FLORIDA STATUTES. | | | | 1. SEE ZONING REVIEW NOTE #1 AND ELECTRICAL REVIEW | | NOTE #3 IN REFERENCE TO THE PLACEMENT OF THE GENERATOR | | AND CORRELATE THE GAS ISOMETRIC IF NEEDED. | | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | NOTE: THIS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE | | REFERENCE THE ATTACHED PERMIT INFORMATION ATTACHED TO | | THE GAS REVIEW INDICATING NAT/GAS AT SAID ADDRESS. | | | | 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | NOTE: THS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE | | REFERENCE THE ATTACHED PERMIT INFORMATION ATTACHED TO | | THE GAS REVIEW INDICATING NAT/GAS AT SAID ADDRESS. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|