Plan Review Notes For Permit 07071047 |
Permit Number |
07071047 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-08 10:54:45 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PROVIDE A LOAD CALCULATION FOR THE | | LOAD INTENDED TO BE SERVED. 215.5. 702.5, 2005NEC | | | | 2} PROVIDE A PANEL SCHEDULE FOR THE | | PANEL AND CIRCUITS SUPPLIED FROM THE GENERATOR. | | 106.3.5.4 FBC AS | | AMENDED, 408.4, 2005 NEC. | | | | 3} THE 5' SETBACK REQUIRED FOR A COMBUSTIBLE SURFACE IS | | NOT BEING MAINTAINED AT THE PROPERTY LINE, IF A FENCE | | OF COMBUSTIBLE MATERIAL IS INSTALLED. ALSO THE BUILDING | | MATERIAL FOR THE RESIDENCE NEEDS TO BE STATED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | 2007-08-08 10:37:32 | | | |
|