Plan Review Notes For Permit 07071044
Permit Number 07071044
Review Stop G
Sequence Number 1
Notes
Date Text
2007-08-13 13:17:27DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. PLEASE REFERENCE ZONING REVIEW NOTES AND ELECTRICAL
 REVIEW NOTE #2 IN REFERENCE TO PLACEMENT OF THE
 GENERATOR AND PLEASE CORRELATE THE GAS DRAWING ON THE
 RESUBMITTAL.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE PERMIT INFORMATION ATTACHED TO THESE GAS
 REVIEW NOTES INDICATING SAID ADDRESS HAS NAT/GAS.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE PERMIT INFORMATION ATTACHED TO THESE GAS
 REVIEW NOTES INDICATING SAID ADDRESS HAS NAT/GAS.
  
 END OF COMMENTS:
  