2007-08-07 16:30:15 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | THIS REVIEW IS FOR COMPLIANCE WITH THE 2005 NEC AND | | THE 2004 FBC, 2006 REVISION. | | | | 1} THE LOAD CALCULATION GIVEN FOR THE PANEL SERVED BY | | THE GENERATOR( 34.1 KW), EXCEEDS THE OUTPUT LOAD OF THE | | 25K GENERATOR THAT WAS SUBMITTED IN VIOLATION OF | | 702.5. | | | | 2} THE 5' SETBACK REQUIRED FOR A COMBUSTABLE SURFACE IS | | NOT BEING MAINTAINED AT THE PROPERTY LINE, IF A WOODEN | | FENCE IS OR COULD BE INSTALLED. ALSO THE BUILDING | | MATERIAL FOR THE RESIDENCE NEEDS TO BE STATED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | | | |
|