Plan Review Notes
Plan Review Notes For Permit 07071039
Permit Number 07071039
Review Stop E
Sequence Number 3
Notes
Date Text
2008-01-03 13:54:452008-01-03
  
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW WITH
 RESPECT TO THE SUBMITTED ENERGY CALCULATIONS AND
 COORDINATION WITH PLANS.
 PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETE WITH THE
 EXTERIOR FIXTURES SUCH AS SITE/PARKING FIXTURES. (THIS
 WATTAGE WAS SHOWN ON SITE PLAN.)
 PLEASE BE SURE ALL FIXTURE WATTAGES AND NUMBER OF
 FIXTURES MATCH.
 PLEASE SEE FOR EXAMPLE: PLANS INDICATE A TOTAL OF
 73-64W FIXTURES, YET ONLY 58 -64 W FIXTURES ARE SHOWN
 ON THE INPUT DATA REPORT.
 PLEASE SEE THE 34 WATT FIXTURES ON THE INPUT DATA
 REPORT ARE NOT LOCATED ON PLANS OR FIXTURE LEGEND. (ARE
 THESE NOT 64W FIXTURES?)
 PLEASE SEE FOR EXAMPLE: THE TOTAL NUMBER OF 32W
 RECESSED LIGHTS ON PLANS IS AT 11 AND IDR SHOWS 9.
 PLEASE SEE THE LIGHTING TOTAL SHOWN ON E2.1 IS HIGHER
 THAN THE TOTAL ON THE IDR. EXAMPLE: PLANS 5408, IDR-
 4510. BOTH ARE LOW.
 13-415.1.A, 13-415.2, 13-415.2.ABC.1.1. .1.2.
  
 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS ARE STILL IN
 QUESTION AS SHOWN. PLEASE SEE THE LIGHTING PLANS FOR
 EXAMPLE SHOWS CORRIDOR LA-16 WHICH SHOWS A NOTE #2
 WHICH MENTIONS TO GO THROUGH LIGHTING CONTACTOR, YET
 THE LIGHTING CONTACTOR DOES NOT SHOW LA-16
 PLEASE CLARIFY THE USE OF MANY OF THE LIGHTING CIRCUITS
 IN SEPARATE SPACES WHICH GOES THROUGH THE LIGHTING
 CONTACTOR SUCH LA-8, LA-36. HOW ARE THESE CONTROLLED BY
 THE LIGHTING CONTACTOR YET THE DEVICES IN THE SPACE
 DOES NOT SEEM TO BE OVER RIDE(S). PLEASE SEE
 13-415.1.ABC.1.2 WHICH REQUIRES SEPARATE SPACES TO
 CONTAIN OVER RIDES. THE SO DEVICES IN OTHER LOCATIONS
 ARE SHOWN AS OVER RIDES, HOWEVER THE SWS DOES NOT SEEM
 TO SHOW THIS AS A OVER RIDE.
 PLEASE CLARIFY.
 13-415.1.ABC.1.1 AND .1.2.
 PLEASE SEE THE OWNER AGENT STILL NEEDS TO SIGN NEW
 CALCULATIONS ONCE RESUBMITTED.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO FS 553.80(2)(B) AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 PLEASE SEE THE SAME CODE SECTIONS ABOVE FOR CHAPTER 13
 APPLY FOR THE THIRD TIME.
 PLEASE BE SURE TO GO OVER PLANS AND COORDINATE ALL.
 PLEASE SEE THE FEE AS REQUIRED UNDER THE FLORIDA
 STATUTES WAS ASSESSED AND IS DUE BEFORE PLANS MAY BE
 RE-SUBMITTED. PLEASE KNOW THAT THE RE-SUB WILL NOT BE
 DUE WHEN RE-SUBMITTING.
 SHEETS E0.1, 2.1 AND 5.1 HAVE BEEN RETAINED ALONG WITH
 ONE COPY OF THE ENERGY CALCULATIONS SUBMITTED.
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2008-01-03 13:53:182008-01-02
  
 NEW ELECTRICAL AND LANDSCAPE SHEETS SUBMITTED.
2008-01-01 16:50:442008-01-01 16:50:44
  
 PLANS IN ELECTRICAL FOR REVIEW.
  