2008-01-03 13:54:45 | 2008-01-03 |
| |
| ** DENIED 3RD REVIEW ** |
| |
| ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW WITH |
| RESPECT TO THE SUBMITTED ENERGY CALCULATIONS AND |
| COORDINATION WITH PLANS. |
| PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETE WITH THE |
| EXTERIOR FIXTURES SUCH AS SITE/PARKING FIXTURES. (THIS |
| WATTAGE WAS SHOWN ON SITE PLAN.) |
| PLEASE BE SURE ALL FIXTURE WATTAGES AND NUMBER OF |
| FIXTURES MATCH. |
| PLEASE SEE FOR EXAMPLE: PLANS INDICATE A TOTAL OF |
| 73-64W FIXTURES, YET ONLY 58 -64 W FIXTURES ARE SHOWN |
| ON THE INPUT DATA REPORT. |
| PLEASE SEE THE 34 WATT FIXTURES ON THE INPUT DATA |
| REPORT ARE NOT LOCATED ON PLANS OR FIXTURE LEGEND. (ARE |
| THESE NOT 64W FIXTURES?) |
| PLEASE SEE FOR EXAMPLE: THE TOTAL NUMBER OF 32W |
| RECESSED LIGHTS ON PLANS IS AT 11 AND IDR SHOWS 9. |
| PLEASE SEE THE LIGHTING TOTAL SHOWN ON E2.1 IS HIGHER |
| THAN THE TOTAL ON THE IDR. EXAMPLE: PLANS 5408, IDR- |
| 4510. BOTH ARE LOW. |
| 13-415.1.A, 13-415.2, 13-415.2.ABC.1.1. .1.2. |
| |
| 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS ARE STILL IN |
| QUESTION AS SHOWN. PLEASE SEE THE LIGHTING PLANS FOR |
| EXAMPLE SHOWS CORRIDOR LA-16 WHICH SHOWS A NOTE #2 |
| WHICH MENTIONS TO GO THROUGH LIGHTING CONTACTOR, YET |
| THE LIGHTING CONTACTOR DOES NOT SHOW LA-16 |
| PLEASE CLARIFY THE USE OF MANY OF THE LIGHTING CIRCUITS |
| IN SEPARATE SPACES WHICH GOES THROUGH THE LIGHTING |
| CONTACTOR SUCH LA-8, LA-36. HOW ARE THESE CONTROLLED BY |
| THE LIGHTING CONTACTOR YET THE DEVICES IN THE SPACE |
| DOES NOT SEEM TO BE OVER RIDE(S). PLEASE SEE |
| 13-415.1.ABC.1.2 WHICH REQUIRES SEPARATE SPACES TO |
| CONTAIN OVER RIDES. THE SO DEVICES IN OTHER LOCATIONS |
| ARE SHOWN AS OVER RIDES, HOWEVER THE SWS DOES NOT SEEM |
| TO SHOW THIS AS A OVER RIDE. |
| PLEASE CLARIFY. |
| 13-415.1.ABC.1.1 AND .1.2. |
| PLEASE SEE THE OWNER AGENT STILL NEEDS TO SIGN NEW |
| CALCULATIONS ONCE RESUBMITTED. |
| |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH |
| RESPECT TO FS 553.80(2)(B) AND REPEAT COMMENTS FOR CODE |
| COMPLIANCE. |
| PLEASE SEE THE SAME CODE SECTIONS ABOVE FOR CHAPTER 13 |
| APPLY FOR THE THIRD TIME. |
| PLEASE BE SURE TO GO OVER PLANS AND COORDINATE ALL. |
| PLEASE SEE THE FEE AS REQUIRED UNDER THE FLORIDA |
| STATUTES WAS ASSESSED AND IS DUE BEFORE PLANS MAY BE |
| RE-SUBMITTED. PLEASE KNOW THAT THE RE-SUB WILL NOT BE |
| DUE WHEN RE-SUBMITTING. |
| SHEETS E0.1, 2.1 AND 5.1 HAVE BEEN RETAINED ALONG WITH |
| ONE COPY OF THE ENERGY CALCULATIONS SUBMITTED. |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |