Plan Review Notes For Permit 07071039 |
Permit Number |
07071039 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-11-14 16:35:21 | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | INSTALLATION OF THE FIRE ALARM SYSTEM DISPLAYED ON THE | | PLANS. | | | | 2. A MANUAL PULL STATION APPEARS TO BE NEEDED ON THE | | REAR EXIT DOOR LOCATED IN THE WORK AREA 120 AS THERE | | APPEARS TO BE ONLY ONE INITIATING APPLIANCE TO ACTIVATE | | THE SYSTEM, MANUAL PULL STATION LOCATED IN THE LOBBY. | | ANOTHER PULL STATION WAS OBSERVED ON PAGE FA2.1. PLEASE | | CORRECT DRAWINGS SO THEY MATCH. LS PLAN AND FA2.1. | | | | 3. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND | | CEILINGS IN THE MEANS OF EGRESS SHALL BE CLASS A SINCE | | THE BUILDING IS NOT FIRE SPRINKLER PROTECTED. | | | | 4. ALL WORK SUBJECT TO FIELD INSPECTION AND APPROVAL BY | | CITY INSPECTORS. | | | | APPROVED PROVISO: | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|