Date |
Text |
2007-10-30 09:55:49 | |
| ** DENIED 2ND REVIEW ** |
| |
| *** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW |
| WHICH ARE STILL IN NEED OF ADDRESSING. |
| PLEASE SEE THAT SOME OF THE EXACT SAME COMMENTS FROM |
| PREVIOUS REVIEW ARE BELOW. |
| PLEASE SEE NEW COMMENT BELOW. |
| |
| |
| 1) NOTE: PLEASE SEE LANDSCAPE PLANS AND FS 481.319 FOR |
| MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| ** THIS IS BEING NOTED ** |
| |
| |
| 2) NOTE: PLEASE SEE COMMENT NUMBER 6 FROM PREVIOUS |
| REVIEW WHICH IS BEING ATTACHED BELOW AND LABELED AS |
| **PREVIOUS REVIEW NOTE **. |
| MANY OF THE SAME ITEMS FROM PREVIOUS REVIEW ARE THE |
| SAME. |
| PLEASE SEE THE LIGHTING CONTROLS ARE NOT COMPLETE AND |
| IN FACT THERE ARE SEVERAL LOCATIONS WHICH STILL |
| INDICATE A STANDARD SWITCH FOR CONTROL. |
| PLEASE SEE THE LIGHTING BEING CONTROLLED MUST BE SEEN |
| BY THE OCCUPANT WHICH IS CONTROLLING THE LIGHTING. |
| PLEASE SEE SHEET E2.1 WHICH CONTAINS A KEY NOTE #2 |
| WHICH MENTIONS TO SEE E0.1 FOR DETAIL, YET E0.1 DOES |
| NOT CONTAIN ANY DETAIL FOR ANY LIGHTING CONTROLS. |
| PLEASE SEE THE LIGHTING ON PLANS DOES NOT CORRELATE |
| WITH THE FIXTURE LEGEND FOR ALL FIXTURES AND DOES NOT |
| CORRELATE WITH THE INPUT DATA REPORT ON THE SUBMITTED |
| ENERGY CALCULATIONS. FOR EXAMPLE: SEE EXTERIOR LIGHTING |
| AS NONE ARE SHOWN ON FIXTURE LEGEND. FOR EXAMPLE: SEE |
| INTERIOR LIGHTING AS THE WATTAGES IS NOT THE SAME. FOR |
| EXAMPLE: COVER SHEET ON ENERGY CALCULATIONS STILL CALL |
| FOR THIS AS A *SHELL BUILDING*. HOW IS THIS POSSIBLE |
| WHEN PLANS DO NOT INDICATE A SHELL BUILDING??? |
| PLEASE BE SURE THE OWNER AGENT IS SIGNED ON |
| CERTIFICATION SHEETS. |
| PLEASE SEE THERE ARE SEVERAL ITEMS AS NOTED ABOVE FOR |
| EXAMPLE ALONG WITH MOST OF THE SAME COMMENTS BELOW FROM |
| PREVIOUS REVIEW WHICH NEED TO BE ADDRESSED. |
| |
| ** PREVIOUS REVIEW NOTE #6 *** |
| PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER 13. |
| PLEASE INDICATE LIGHTING CONTROLS PER |
| 13-415.1.ABC.1.1, .1.2. |
| PLANS INDICATE A TIME CLOCK HOWEVER LOCATIONS FOR ALL |
| OVER RIDES AS REQUIRED COULD NOT BE FOUND ON PLANS. |
| PLEASE SEE THERE IS SEPARATE SPACE CONTROL MISSING FOR |
| MANY AREAS. |
| PLEASE SEE NO TIME SCHEDULING WAS SUBMITTED. PLEASE SEE |
| NO MAXIMUM OVER RIDE TIMES WERE INDICATED (DEVICES NOT |
| SHOWN) |
| PLEASE BE SURE ALL DEVICES WHICH WILL BE IN DESIGN AND |
| ON PLANS ARE STATED ON LEGEND FOR DEVICES. |
| PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT |
| CORRELATE WITH THE PLANS AND DESIGN. THESE INDICATE |
| BUILDING BEING A *SHELL* WHEN IN FACT THE BUILDING IS |
| BEING BUILT OUT AT THIS TIME. PLEASE ALSO SEE THE INPUT |
| DATA REPORT DOES NOT CORRELATE WITH PLANS. |
| PLEASE SEE THE TYPE OF FIXTURES. |
| PLEASE SEE THE NUMBER OF FIXTURES |
| PLEASE SEE THE WATTAGE OF FIXTURES. |
| PLEASE SEE NO EXTERIOR LIGHTING WAS INPUTTED IN THE IDR |
| WHEN THE PLANS CONTAIN EXTERIOR LIGHTS. |
| PLEASE BE SURE THE METHOD OF CONTROLS IS COORDINATED |
| WITH PLANS AND DESIGN FOR THE METHOD OF CONTROL. SHOWN |
| AS *MANUAL ON/OFF* WHICH IS NOT POSSIBLE AS THE PLANS |
| ARE REQUIRED AND CONTAIN AUTOMATED CONTROLS. |
| THERE ARE SEVERAL ITEMS ON THE CALCULATIONS WHICH NEED |
| TO BE ADDRESSED. |
| |
| PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO |
| ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA |
| COORDINATES WITH THE PLANS. |
| PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS |
| PER 13-415.2. |
| PLEASE KNOW AT THIS TIME NO REVIEW FOR LIGHTING |
| COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR |
| LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.2, |
| 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1 |
| |
| 3) NOTE: PLEASE SEE THIS COMMENT FROM PREVIOUS REVIEW |
| WILL REMAIN AS NOT ALL FIXTURES ON CALCULATIONS, |
| FIXTURE LEGEND AND PLANS ARE THE SAME. |
| FBC 106.1.2 FOR COORDINATION/ADDITIONAL INFORMATION. |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON PLANS AND |
| CORRELATE WITH THE LEGEND. |
| PLEASE SEE SOME FIXTURES COULD NOT BE IDENTIFIED FOR |
| EMERGENCY USE ALTHOUGH THIS IS ONLY ASSUMED AT THIS |
| TIME DUE TO THE SHADING ON PLANS. |
| |
| 4) NOTE: PLEASE SEE DISCONNECTS LOCATED OUTSIDE FOR THE |
| CONDENSING UNITS DO NOT MEET 110.26 FOR MINIMUM WIDTHS |
| OR DEPTHS. THIS IS THE SAME COMMENT. BASED ON THE PLANS |
| AND SCALE ON SHEETS, THESE DO NOT MEET THE MINIMUM |
| 30X36 INCHES REQUIRED. |
| PLEASE ADJUST AND PLEASE BE SURE TO ADJUST OTHER SHEETS |
| FOR RELEVANT SET-BACKS AND DIMENSIONS. |
| |
| 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOE CODE COMPLIANCE. THIS IS ONLY A |
| NOTICE GIVEN AT THIS TIME. |
| ONE COPY OF ELECTRICAL PLANS AND ENERGY CALCULATIONS |
| HAVE BEEN RETAINED. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |