Plan Review Notes
Plan Review Notes For Permit 07071039
Permit Number 07071039
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-30 09:55:49 
 ** DENIED 2ND REVIEW **
  
 *** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE SEE THAT SOME OF THE EXACT SAME COMMENTS FROM
 PREVIOUS REVIEW ARE BELOW.
 PLEASE SEE NEW COMMENT BELOW.
  
  
 1) NOTE: PLEASE SEE LANDSCAPE PLANS AND FS 481.319 FOR
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 ** THIS IS BEING NOTED **
  
  
 2) NOTE: PLEASE SEE COMMENT NUMBER 6 FROM PREVIOUS
 REVIEW WHICH IS BEING ATTACHED BELOW AND LABELED AS
 **PREVIOUS REVIEW NOTE **.
 MANY OF THE SAME ITEMS FROM PREVIOUS REVIEW ARE THE
 SAME.
 PLEASE SEE THE LIGHTING CONTROLS ARE NOT COMPLETE AND
 IN FACT THERE ARE SEVERAL LOCATIONS WHICH STILL
 INDICATE A STANDARD SWITCH FOR CONTROL.
 PLEASE SEE THE LIGHTING BEING CONTROLLED MUST BE SEEN
 BY THE OCCUPANT WHICH IS CONTROLLING THE LIGHTING.
 PLEASE SEE SHEET E2.1 WHICH CONTAINS A KEY NOTE #2
 WHICH MENTIONS TO SEE E0.1 FOR DETAIL, YET E0.1 DOES
 NOT CONTAIN ANY DETAIL FOR ANY LIGHTING CONTROLS.
 PLEASE SEE THE LIGHTING ON PLANS DOES NOT CORRELATE
 WITH THE FIXTURE LEGEND FOR ALL FIXTURES AND DOES NOT
 CORRELATE WITH THE INPUT DATA REPORT ON THE SUBMITTED
 ENERGY CALCULATIONS. FOR EXAMPLE: SEE EXTERIOR LIGHTING
 AS NONE ARE SHOWN ON FIXTURE LEGEND. FOR EXAMPLE: SEE
 INTERIOR LIGHTING AS THE WATTAGES IS NOT THE SAME. FOR
 EXAMPLE: COVER SHEET ON ENERGY CALCULATIONS STILL CALL
 FOR THIS AS A *SHELL BUILDING*. HOW IS THIS POSSIBLE
 WHEN PLANS DO NOT INDICATE A SHELL BUILDING???
 PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 CERTIFICATION SHEETS.
 PLEASE SEE THERE ARE SEVERAL ITEMS AS NOTED ABOVE FOR
 EXAMPLE ALONG WITH MOST OF THE SAME COMMENTS BELOW FROM
 PREVIOUS REVIEW WHICH NEED TO BE ADDRESSED.
  
 ** PREVIOUS REVIEW NOTE #6 ***
 PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER 13.
 PLEASE INDICATE LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2.
 PLANS INDICATE A TIME CLOCK HOWEVER LOCATIONS FOR ALL
 OVER RIDES AS REQUIRED COULD NOT BE FOUND ON PLANS.
 PLEASE SEE THERE IS SEPARATE SPACE CONTROL MISSING FOR
 MANY AREAS.
 PLEASE SEE NO TIME SCHEDULING WAS SUBMITTED. PLEASE SEE
 NO MAXIMUM OVER RIDE TIMES WERE INDICATED (DEVICES NOT
 SHOWN)
 PLEASE BE SURE ALL DEVICES WHICH WILL BE IN DESIGN AND
 ON PLANS ARE STATED ON LEGEND FOR DEVICES.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE PLANS AND DESIGN. THESE INDICATE
 BUILDING BEING A *SHELL* WHEN IN FACT THE BUILDING IS
 BEING BUILT OUT AT THIS TIME. PLEASE ALSO SEE THE INPUT
 DATA REPORT DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE THE TYPE OF FIXTURES.
 PLEASE SEE THE NUMBER OF FIXTURES
 PLEASE SEE THE WATTAGE OF FIXTURES.
 PLEASE SEE NO EXTERIOR LIGHTING WAS INPUTTED IN THE IDR
 WHEN THE PLANS CONTAIN EXTERIOR LIGHTS.
 PLEASE BE SURE THE METHOD OF CONTROLS IS COORDINATED
 WITH PLANS AND DESIGN FOR THE METHOD OF CONTROL. SHOWN
 AS *MANUAL ON/OFF* WHICH IS NOT POSSIBLE AS THE PLANS
 ARE REQUIRED AND CONTAIN AUTOMATED CONTROLS.
 THERE ARE SEVERAL ITEMS ON THE CALCULATIONS WHICH NEED
 TO BE ADDRESSED.
  
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA
 COORDINATES WITH THE PLANS.
 PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS
 PER 13-415.2.
 PLEASE KNOW AT THIS TIME NO REVIEW FOR LIGHTING
 COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR
 LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.2,
 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1
  
 3) NOTE: PLEASE SEE THIS COMMENT FROM PREVIOUS REVIEW
 WILL REMAIN AS NOT ALL FIXTURES ON CALCULATIONS,
 FIXTURE LEGEND AND PLANS ARE THE SAME.
 FBC 106.1.2 FOR COORDINATION/ADDITIONAL INFORMATION.
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE LEGEND.
 PLEASE SEE SOME FIXTURES COULD NOT BE IDENTIFIED FOR
 EMERGENCY USE ALTHOUGH THIS IS ONLY ASSUMED AT THIS
 TIME DUE TO THE SHADING ON PLANS.
  
 4) NOTE: PLEASE SEE DISCONNECTS LOCATED OUTSIDE FOR THE
 CONDENSING UNITS DO NOT MEET 110.26 FOR MINIMUM WIDTHS
 OR DEPTHS. THIS IS THE SAME COMMENT. BASED ON THE PLANS
 AND SCALE ON SHEETS, THESE DO NOT MEET THE MINIMUM
 30X36 INCHES REQUIRED.
 PLEASE ADJUST AND PLEASE BE SURE TO ADJUST OTHER SHEETS
 FOR RELEVANT SET-BACKS AND DIMENSIONS.
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOE CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 ONE COPY OF ELECTRICAL PLANS AND ENERGY CALCULATIONS
 HAVE BEEN RETAINED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-29 16:38:33 
  
 IN ELEC FOR REVIEW.