Plan Review Notes
Plan Review Notes For Permit 07071039
Permit Number 07071039
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-24 17:22:38REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M0.1 MECH NOTES #12: THERMOSTATIC CONTROLS SHALL
 COMPLY WITH FBC 13-407.1.ABC.2.4.1.
  
 2. M0.1 AIR BALANCE SCHEDULE: AHU #5 IS MISSING FROM
 THE SCHEDULE. PLEASE CORRECT AND RESUBMIT.
  
 3. M0.1 FAN SCHEDULE: CONTROLS INDICATE "LIGHT
 INTERLOCK." PROVISIONS SHALL ALSO BE MADE TO INTERLOCK
 FANS WITH AHU #4 TO ASSURE THAT ALL AIR SUPPLIED TO THE
 TOILET ROOMS IS EXHAUSTED AND NOT RECIRCULATED IN
 ACCORDANCE WITH FBC,M 403.2.1(3).
  
 4. M2.1: AHU #4 ON FLOOR PLAN SHOWS 1330 CFM WHILE AHU
 #5 SHOWS 1050 CFM. EQUIPMENT SCHEDULE CALLS FOR 1200
 CFM EACH. PERHAPS ONE OR MORE DROPS IS ATTACHED TO THE
 WRONG SYSTEM. SHOW AN AIR BALANCE WHICH IS IN
 CONJUNCTION WITH EQUIPMENT SCHEDULE.
  
 5. M5.1: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 6. M5.1: LOUVER DETAIL INDICATES A MIAMI-DADE NOA WHICH
 HAS EXPIRED. PROVIDE AN UPDATED FLORIDA PRODUCT
 APPROVAL OR NOA SUBMITTAL.
  
 7. M5.1: AHU DETAIL SHOWS LOUVERED DOORS BUT FLOOR PLAN
 SHOWS SOLID DOORS WITH WALL GRILL. PLEASE COORDINATE
 PLANS.
  
 8. ENERGY CALCULATIONS: THIS SPACE IS NOT COOLED BY ONE
 SYSTEM OF 240,000 TO 760,000 BTU/H COOLING CAPACITY.
 ADJUST CALCULATIONS TO ACCURATELY REFLECT THE EQUIPMENT
 BEING USED AND THE MINIMUM EFFICIENCY RATING REQUIRED.
 EXAMPLE: FOR EQUIPMENT <65,000 BTU/H THE EFFICIENCY
 CRITERIA IS 13.00 NOT 9.50 AS STATED ON CALCULATIONS
 SYSTEM REPORT.
  
 9. ROOF TYPE ON INPUT DATA REPORT SHOWS A METAL
 BUILDING ROOF WITH R-19 BATTS. THIS IS NOT A METAL
 BUILDING AND THERE ARE NO BATTS AT THE ROOF. PLEASE
 CORRECT TO ACCURATELY REFLECT THE SYSTEM BEING USED ON
 THIS BUILDING AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  