Plan Review Notes
Plan Review Notes For Permit 07071039
Permit Number 07071039
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-25 19:54:092007-08-25 19:54:09
  
 *** DENIED ***
  
 ** PLEASE KNOW AS SOME INFORMATION WAS NOT YET
 SUBMITTED A COMPLETE AND FULL REVIEW FOR SOME ITEMS
 COULD NOT BE DONE.
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS BELOW (2,3,4
 AND 5) WHICH DO NOT PERTAIN TO KAMM CONSULTING
 ENGINEERING.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE
 BLOCKS FOR THE LANDSCAPE PLANS.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 AND INFORMATION AS REQUIRED PER 61G1-16.004. PLEASE SEE
 FS 481.219 FOR REQUIRED MISSING CA #.
  
 3) NOTE: PLEASE SEE ALL SHEETS OF THE SUBMITTED
 LANDSCAPE PLANS ARE IN FACT *PHOTO-COPIES* OF SIGNED
 AND SEALED PLANS.
 PLEASE BE SURE TO SIGN, DATED AND SEALED PLANS WITH THE
 REQUIRED RAISED SEAL AND ORIGINAL SIGNATURE. PLEASE SEE
 FS 481.221, AND PLEASE SEE FAC 61G1-16.002 FOR CORRECT
 SEAL AS REQUIRED.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 4) NOTE: PLEASE SEE THE CIVIL PLANS SUBMITTED ARE NOT
 SIGNED, DATED AND SEALED AS REQUIRED PER FAC
 61G15-23.002, FS 471.025
 PLEASE ALSO SEE MISSING INFORMATION AS REQUIRED ON
 TITLE BLOCKS ARE REQUIRED PER FAC 61G15-23.002.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 5) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE
 BLOCKS ON THE *S* SHEETS.
 PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED PER FAC 61G15-23.002, FS 471.023
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 6) NOTE: PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER
 13.
 PLEASE INDICATE LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2.
 PLANS INDICATE A TIME CLOCK HOWEVER LOCATIONS FOR ALL
 OVER RIDES AS REQUIRED COULD NOT BE FOUND ON PLANS.
 PLEASE SEE THERE IS SEPARATE SPACE CONTROL MISSING FOR
 MANY AREAS.
 PLEASE SEE NO TIME SCHEDULING WAS SUBMITTED. PLEASE SEE
 NO MAXIMUM OVER RIDE TIMES WERE INDICATED (DEVICES NOT
 SHOWN)
 PLEASE BE SURE ALL DEVICES WHICH WILL BE IN DESIGN AND
 ON PLANS ARE STATED ON LEGEND FOR DEVICES.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE PLANS AND DESIGN. THESE INDICATE
 BUILDING BEING A *SHELL* WHEN IN FACT THE BUILDING IS
 BEING BUILT OUT AT THIS TIME. PLEASE ALSO SEE THE INPUT
 DATA REPORT DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE THE TYPE OF FIXTURES.
 PLEASE SEE THE NUMBER OF FIXTURES
 PLEASE SEE THE WATTAGE OF FIXTURES.
 PLEASE SEE NO EXTERIOR LIGHTING WAS INPUTTED IN THE IDR
 WHEN THE PLANS CONTAIN EXTERIOR LIGHTS.
 PLEASE BE SURE THE METHOD OF CONTROLS IS COORDINATED
 WITH PLANS AND DESIGN FOR THE METHOD OF CONTROL. SHOWN
 AS *MANUAL ON/OFF* WHICH IS NOT POSSIBLE AS THE PLANS
 ARE REQUIRED AND CONTAIN AUTOMATED CONTROLS.
 THERE ARE SEVERAL ITEMS ON THE CALCULATIONS WHICH NEED
 TO BE ADDRESSED.
  
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA
 COORDINATES WITH THE PLANS.
 PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS
 PER 13-415.2.
 PLEASE KNOW AT THIS TIME NO REVIEW FOR LIGHTING
 COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR
 LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.2,
 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1
  
 7) NOTE: PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE LEGEND.
 PLEASE SEE SOME FIXTURES COULD NOT BE IDENTIFIED FOR
 EMERGENCY USE ALTHOUGH THIS IS ONLY ASSUMED AT THIS
 TIME DUE TO THE SHADING ON PLANS.
  
 8) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL. PLEASE SEE THE USE OF *RECEPTACLES AND
 LIGHTING * ON PANEL SCHEDULE DOES NOT PROVIDE THE
 DETAILED INFORMATION NEEDED.
 PLEASE KNOW THESE CAN BE ALPHA OR NUMERIC DESIGNATIONS
 IF THIS HELPS TO ALLEVIATE CONGESTION ON PLANS.PLEASE
 SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE CODE
 WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS INDICATES
 THE FPL TRANSFORMER IN ONE LOCATION AT THE REAR OF THE
 PROPERTY AND THE ELECTRICAL PLANS INDICATES THIS SAME
 TRANSFORMER AT THE FRONT ENTRANCE.
 THIS LOCATION CONTAINS THE FPL POLES AT THE REAR OF
 PROPERTY. PLEASE COORDINATE AND ADJUST PLANS.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE MISSING SIGN CIRCUIT REQUIRED AT
 THE FRONT ENTRANCE PER 600.5.
 PLEASE BE SURE TO ADJUST THE CALCULATIONS TO THE
 MINIMUM LOAD OF 1200 VA.
  
 11) NOTE: PLEASE CLARIFY THE REQUIRED DISCONNECTING
 MEANS FOR AIR HANDLER UNITS INSIDE BUILDING PER
 440.11.
  
 12) NOTE: PLEASE SEE DISCONNECTS LOCATED OUTSIDE FOR
 THE CONDENSING UNITS DO NOT MEET 110.26 FOR MINIMUM
 WIDTHS OR DEPTHS.
 PLEASE ADJUST.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]