2007-09-08 10:41:15 | BUILDING PLAN REVIEW |
| PERMIT: 07071039 |
| ADD: 234 SOUTHERN BLVD |
| CONT: LEONARD ALBANESE & SONS BUILDERS, INC |
| TEL: (561)239-2034 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1SRREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT |
| --- |
| PLEASE DO NOT |
| IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) SLATTERY & ASSOCIATES ARCHITECTSPLANNERS, |
| 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A |
| REGISTERED ARCHITECT SHALL |
| INCLUDE A TITLE BLOCK WHICH MUST: |
| - STATE THE FIRM NAME, ADDRESS AND |
| TELEPHONE NUMBER |
| - STATE THE FIRM LICENSE NUMBER |
| - STATE PROJECT NAME OR IDENTIFICATION - |
| STATE DATE PREPARED |
| - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL |
| XX- INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING |
| THE PLANS, NOTE THE |
| FLORIDA REGISTRATION NUMBER BY THE RAISED |
| SEAL IS THE CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| |
| 4) STRUCTURAL PLANS, THE ENGINEERING FORM SA-TECH |
| ENGINEERING, INC. HASN?T INCLUDED THEIR CERTIFICATE OF |
| AUTHORIZATION.471.023 F.S.CERTIFICATE OF |
| AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING |
| THE NAME OF AN ENGINEER |
| PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL |
| INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| |
| 5) STRUCTURAL SHEETS ARE MISSING INFORMATION IN THE |
| TITLE BLOCK: |
| SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET |
| CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND |
| LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS |
| AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. |
| |
| 6) A WARRANTY DEED WAS SUBMITTED AS PROOF OF OWNERSHIP, |
| IN THIS DOCUMENT IT INDICATES (2) PARCELS PARCEL A & |
| PARCEL B. THE PERMIT APPLICATION INDICATES THIS |
| BUILDING IS BEING BUILT ON LOT 285 BUT IN LOOKING AT |
| THE PROPERTY TAX MAPS IT APPEARS THAT THE STRUCTURE |
| TRANSGRESSES THE PROPERTY LINE ON TO LOT 291 ALSO, A |
| UNITY OF TITLE WILL BE REQUIRED. THE PROPOSED BUILDING |
| STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE |
| LOTS WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF |
| TITLE' SHALL BE RECORDED AT THE COUNTY COURTHOUSE. |
| SUBMIT A COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT |
| SO THAT FBC TABLE 600 BOUNDARY LINE REQUIREMENTS MAY BE |
| DEEMED NOT APPLICABLE. |
| |
| 7) 106.1.2* ADDITIONAL INFORMATION IS REQUIRED. THE |
| COVER SHEET INDICATES THE OWNERS TO BE LOCKS OF LOVE, |
| INC.THE PLANS INDICATE THIS TO BE A BUSINESS |
| OCCUPANCY AND THE PLANS ONLY INDICATE THE USE OF THE |
| ROOMS AS OFFICES. PLEASE IDENTIFY THE ROOMS WHICH WILL |
| BE USING X-RAY EQUIPMENT THIS ASSUMPTION IS MADE |
| BECAUSE OF THE CODE CRITERIA FOUND ON A-001 REPORT# 34 |
| MEDICAL X-RAY AND GAMMA RAY. PLEASE PROVIDE ADDITIONAL |
| INFORMATION. MORE COMMENTS MAY APPEAR ON THE NEXT |
| REVIEW DEALING WITH THIS ISSUE. |
| |
| 8) A SINGLE SIGNED AND SEALEDGFA INTERNATIONAL |
| GEOTECHNICALREPORT WAS SUBMITTED, TWO ORIGINAL SIGNED |
| AND SEALED REPORTS ARE REQUIRED. |
| |
| 9)THERE SEEMS TO BE A DISCREPANCY BETWEEN THE PERMIT |
| APPLICATION WORK TO BE COMPLETED UNDER THIS BUILDING |
| AND THE ENERGY EFFICIENCY CODE ENERGY CALCS. |
| THE ENERGY CALCULATIONS ARE STATING THAT THEY ARE FOR A |
| SHELL BUILDING ONLY, IS THIS |
| THE SCOPE OF WORK FOR THE BUILDING.IS THE PERMIT |
| APPLICATION WRONG IN SCOPE OF WORK OR THE ENERGY |
| CALCULATIONS? |
| 10) THE ENERGY CALCULATIONS INDICATE THIS IS TO BE A |
| METAL ROOF WHERE AS THE PLANS CALL FOR A SPANISH **S** |
| CONCRETE TILE ROOF PLEASE CORRECT. |
| |
| 11) THE ENERGY CALCULATIONS SHOULD ALSO CORRECT THE |
| WINDOW SECTION OF HE CALCS, THE PLANS ELEVATIONS ARE |
| LABELED BACKWARDSNORTH IS SOUTH AND EAST IS WEST, |
| PLEASE CORRECT BOTH THE PLANS AND ENERGY CALCULATIONS. |
| DISCREPANCIES. |
| |
| 12) PLEASE ALSO CORRECT THE ENERGY CALCULATIONS AS TO |
| TYPE OF INSULATION ENERGY CALCULATIONS INDICATE THE USE |
| OF R-19 INSULATION- BATT WHERE AS THE PLAN INDICATES |
| THE USE OF ICYNENE BUT NO R FACTOR OR DEPTH IS |
| PROVIDED, PLEASE CORRECT BOTH ISSUES. DISCREPANCIES. |
| |
| |
| 13) SHEET A-601 WINDOW BUCKS ARE INDICATED AS TAPERED |
| BUCKS NOT HAVING SUPPORT BY BOTH FACES OF THE WINDOW |
| FRAME.1714.5.4.2 MASONRY, CONCRETE OR OTHER |
| STRUCTURAL SUBSTRATE.UNLESS OTHERWISE TESTED, BUCKS |
| SHALL EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR |
| DOOR FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS |
| PROVIDED. SHIMS SHALL BE MADE FROM MATERIALS CAPABLE OF |
| SUSTAINING APPLICABLE LOADS, LOCATED AND APPLIED IN A |
| THICKNESS CAPABLE OF SUSTAINING APPLICABLE LOADS. |
| ANCHORS SHALL BE PROVIDED TO TRANSFER LOAD FROM THE |
| WINDOW OR DOOR FRAME TO THE ROUGH OPENING SUBSTRATE. |
| |
| 14) SHEET A-901 DOOR SCHEDULE THIS IS PROBABLY A TYPE-0 |
| SEE DOOR HEIGHT OF DOOR # 113, 5?-6?. |
| |
| 15) SHEET A-901 ROOM SCHEDULE WALL AROUND THE WATER |
| CLOSETS INDICATES THE USE OF GYPSUM WALL BOARD, PLEASE |
| SEE: 1210.2 WALLS. SMOOTH, HARD, NONABSORBENT SURFACE, |
| TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND |
| EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN |
| SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY |
| AFFECTED BY MOISTURE. |
| |
| 16) SHEET A-201 ROOM 113 INDICATES A BREAK ROOM WITH |
| SINK, THE PLANS DO NOT HAVE ANY ELEVATIONS OF THE |
| CABINETRY PLEASE PROVIDE ELEVATIONS COMPLYING WITH: |
| SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED |
| WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH |
| FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH |
| 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH |
| SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| SINK. |
| |
| 17) SHEET A-201 IS MISSING ATTIC ACCESS:1209.2 ATTIC |
| SPACES. |
| AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM |
| BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A |
| CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 |
| MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE |
| PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| |
| 18) SHEET A-01 VERTICAL WALL REINFORCING NOTE # 5 |
| INDICATES ADDITIONAL # 5?S AS VERTICAL REINFORCING, |
| WHERE IS NOTE FOR THE CENTER TO CENTER VERTICAL |
| REINFORCING. ACI 530. |
| |
| 19) SHEET S-06 NOTE# 5 MASONRYSUB-NOTE JSECTION |
| 2122.4THIS IS HIGH VELOCITY HURRICANE, ZONE BROWARD |
| AND DADE COUNTIES PLEASE CORRECT. |
| |
| 20) SHEET S-06 STRUCTURAL NOTES 6-E INDICATE ROOF |
| SHEATHING TO COMPLY WITH 2322.2 THIS IS HIGH VELOCITY |
| HURRICANE, ZONE BROWARD AND DADE COUNTIES PLEASE |
| CORRECT. |
| |
| 21) SHEET S-06 NOTE # 9 DELEGATED ENGINEERING |
| RESPONSIBILITIES |
| NOTE # 9, 2319.17.2.1. AGAIN HIGH WIND HURRICANE ZONE, |
| BROWARD AND |
| DADE COUNTIES, PLEASE CORRECT. |
| |
| 22) SHEET S-06 NOTE# 12 CONDUITS AND PIPES EMBEDDED IN |
| CONCRETE |
| NOTE# 5 1925.3,2 THIS IS HIGH VELOCITY HURRICANE, |
| ZONE BROWARD AND DADE COUNTIES PLEASE CORRECT. |
| |
| 23) SHEET E1.1 ELECTRIC LIGHT POLE DETAIL PLEASE |
| REMEMBER THAT WHEN THE POLE SUPPLIER IS PROVIDING THE |
| LIGHT POLETHE DESIGN IS 140 MPH WITH A |
| EXPOSURE **C** CATEGORY. |
| |
| 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PLEASE PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, (3) |
| IF PROJECT REQUIRES A THRESHOLD OR SPECIAL INSPECTOR , |
| MISSING REPORTS ARE AS FOLLOWS: |
| A) PICTURE WINDOW- REQUIRES FLORIDA COVER SHEET, |
| UPDATE TO CURRENT NOA OR |
| DIVIDE THE PRESSURES BY 1.33 OLDER NOA BEFORE |
| 2004 TOOK 1.33 STEEL |
| INCREASES IN FASTENERSOR HAVE ENGINEER CERTIFY |
| FASTENERS. |
| B) STORE FRONT-- REQUIRES FLORIDA COVER SHEET,C) |
| GLAZED EXTERIOR DOORS- REQUIRES FLORIDA COVER SHEET, |
| UPDATE TO CURRENT NOA OR DIVIDE THE PRESSURES BY 1.33 |
| OLDER NOA BEFORE 2004 TOOK 1.33 |
| STEEL INCREASES IN FASTENERSOR HAVE ENGINEER |
| CERTIFY FASTENERS |
| D) EXTERIOR METAL DOORS- NO REPORT SUBMITTED |
| E) TRUSS ANCHORS- NO REPORT SUBMITTED |
| F) ROOF ASSEMBLIES: |
| TILE : REQUIRES REPORT HIGHLIGHT TYPE OF ATTACHMENT |
| TO ROOF |
| UNDERLAYMENTS- REQUIRES BACKUP REPORT |
| |
| 25) THIS SUBMITTAL DOESN'T INCORPORATE ANY ROOFING |
| PRODUCT APPROVALS, HERE IS A LIST OF COMMON ISSUES THAT |
| WILL FAIL A ROOFING REPORT SUBMITTAL:THIS ROOF IS |
| MISSING OR NOT INCOMPLIANCE WITH THE FOLLOW |
| ITEMS: |
| _XX__ CONTRACTOR FAILED TO PROVIDE BACK UP ROOFING |
| REPORT DOCUMENTATION |
| ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF HEIGHT. |
| ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _XX__ |
| CONTRACTOR FAILED TO INDICATE WHICH SYSTEM OR SUBSYSTEM |
| WILL BE USED. |
| _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| _2__ . |
| _XX__ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS |
| DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| SPACING, PREPAREDSIGNEDAND SEALED BY A FLORIDA |
| REGISTEREDPROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| SUBMITTED. |
| ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| ENHANCED FASTENING ALLOWED. |
| |
| 26) PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER |
| RULE 9B-72. |
| |
| 27) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 28)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 29) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION |
| MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT |
| ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS |
| SERVING |
| ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE |
| DESIGN COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE |
| THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING |
| IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND |
| AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE |
| A |
| PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY |
| INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON |
| COMPLETION OF THE |
| IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER |
| SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE |
| APPROVAL OF THE FINAL INSPECTION. |
| |
| 30) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION |
| TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| SECTION 113 OF THIS CHAPTER. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| |
| |
| |
| |