Date |
Text |
2007-10-12 17:26:50 | RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST. |
| REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE, 2004 |
| EXISTING BUILDING CODE AND 2004 FBC. |
| |
| 1- RECORDED NOTICE OF COMMENCEMENT SUBMITTED STATES |
| THAT EXPIRATION DATE IS SEPTEMBER, 25, 2007.REVISE |
| EXPIRATION DATE AND RE-RECORD DOCUMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| 2- CHANCE HELICAL PIER FOUNDATION SYSTEM REQUIRES |
| PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72. |
| INFORMATION SUBMITTED IS NOT AN APPROVED FLORIDA |
| PRODUCT APPROVAL. PROVIDE EITHER A FLORIDA PRODUCT |
| APPROVAL OR DADE COUNTY NOA. THEN, ARCHITECT TO REVIEW |
| AND APPROVE SUCH PRODUCT APPROVAL AS REQUIRED BY SEC. |
| 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 3-A) CHANCE HELICAL PIER FOUNDATION SYSTEM REQUIRES |
| COMPLETE ENGINEERING ANALYSIS AS REQUIRED BY |
| INFORMATION SUBMITTED AND BY NOTE ON FOUNDATION PLAN |
| SHEET S-1. PROVIDE COMPLETE INFORMATION. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| B) PROVIDE SOIL TEST REPORT AS REQUIRED BY |
| INFORMATION SUBMITTED AND REQUIREDFOR ENGINEER |
| ANALYSIS OF THIS FOUNDATION SYSTEM. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 4- TYP. STAIR DETAIL 4/A3 DOESN'T MATCH PLANS. REVISE |
| AS REQUIRED AND SHOW HANDRAIL HEIGHT TO VERIFY |
| COMPLIANCE WITH SEC.R311.5.6.1 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| 5- SHEET S-1: REVISE ALL STRUCTURAL CONNECTORS |
| USP/SIMPSON SPECIFIED ON FIRST FLOOR AND LOW ROOF |
| FRAMING/BRACING PLAN. NEED TO SPECIFYWOOD TO MASONRY |
| CONNECTORS WHERE REQUIRED. REVISE PLAN AND DETAILS ON |
| SHEET S-2 AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO |
| FBC 2004. REPEAT COMMENT. |
| |
| ***NOTE: SEE CATALOG FOR PROPER CONNECTORS THAT ARE |
| DESIGNED FOR WOOD TO MASONRY APPLICATIONS. CONNECTORS |
| SPECIFIED ON PLAN AREDESIGNED FOR WOOD TO WOOD |
| APPLICATIONS. ALSO, PROVIDE COMPLETE ENGINEERING |
| ANALYSIS FOR NUMBER AND TYPE OF FASTENERS THAT DIFFER |
| FROM THOSE TESTED AND PUBLISHED BY THE MANUFACTURER. |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 6- POLYSET ROOF TILE ADHESIVE NOA 04-1116.01 SUBMITTED |
| CAN'T BE USED FOR THE ROOF TILE NOA SUBMITTED BECAUSE |
| IT NEEDS TO BE LISTED IN THE ROOF TILE NOA IN ORDER TO |
| VERIFY THE MOMENT OF RESISTANCE. SEE LIMITATIONS ON |
| POLYSET NOA SUBMITTED.NEED TO PROVIDE PRODUCT |
| APPROVAL FOR ADHESIVE THAT IS LISTED IN THE ROOF TILE |
| PRODUCT APPROVAL. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| ALSO, REVISE ROOF ATTACHMENT DETAIL ON SHEET S-2 AS |
| REQUIRED TO MATCH PRODUCT APPROVALS SUBMITTED. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |