2007-10-12 17:26:50RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE, 2004
 EXISTING BUILDING CODE AND 2004 FBC.
  
 1- RECORDED NOTICE OF COMMENCEMENT SUBMITTED STATES
 THAT EXPIRATION DATE IS SEPTEMBER, 25, 2007.REVISE
 EXPIRATION DATE AND RE-RECORD DOCUMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- CHANCE HELICAL PIER FOUNDATION SYSTEM REQUIRES
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72.
 INFORMATION SUBMITTED IS NOT AN APPROVED FLORIDA
 PRODUCT APPROVAL. PROVIDE EITHER A FLORIDA PRODUCT
 APPROVAL OR DADE COUNTY NOA. THEN, ARCHITECT TO REVIEW
 AND APPROVE SUCH PRODUCT APPROVAL AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 3-A) CHANCE HELICAL PIER FOUNDATION SYSTEM REQUIRES
 COMPLETE ENGINEERING ANALYSIS AS REQUIRED BY
 INFORMATION SUBMITTED AND BY NOTE ON FOUNDATION PLAN
 SHEET S-1. PROVIDE COMPLETE INFORMATION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 B) PROVIDE SOIL TEST REPORT AS REQUIRED BY
 INFORMATION SUBMITTED AND REQUIREDFOR ENGINEER
 ANALYSIS OF THIS FOUNDATION SYSTEM. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 4- TYP. STAIR DETAIL 4/A3 DOESN'T MATCH PLANS. REVISE
 AS REQUIRED AND SHOW HANDRAIL HEIGHT TO VERIFY
 COMPLIANCE WITH SEC.R311.5.6.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- SHEET S-1: REVISE ALL STRUCTURAL CONNECTORS
 USP/SIMPSON SPECIFIED ON FIRST FLOOR AND LOW ROOF
 FRAMING/BRACING PLAN. NEED TO SPECIFYWOOD TO MASONRY
 CONNECTORS WHERE REQUIRED. REVISE PLAN AND DETAILS ON
 SHEET S-2 AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004. REPEAT COMMENT.
  
 ***NOTE: SEE CATALOG FOR PROPER CONNECTORS THAT ARE
 DESIGNED FOR WOOD TO MASONRY APPLICATIONS. CONNECTORS
 SPECIFIED ON PLAN AREDESIGNED FOR WOOD TO WOOD
 APPLICATIONS. ALSO, PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR NUMBER AND TYPE OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE MANUFACTURER.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 6- POLYSET ROOF TILE ADHESIVE NOA 04-1116.01 SUBMITTED
 CAN'T BE USED FOR THE ROOF TILE NOA SUBMITTED BECAUSE
 IT NEEDS TO BE LISTED IN THE ROOF TILE NOA IN ORDER TO
 VERIFY THE MOMENT OF RESISTANCE. SEE LIMITATIONS ON
 POLYSET NOA SUBMITTED.NEED TO PROVIDE PRODUCT
 APPROVAL FOR ADHESIVE THAT IS LISTED IN THE ROOF TILE
 PRODUCT APPROVAL. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 ALSO, REVISE ROOF ATTACHMENT DETAIL ON SHEET S-2 AS
 REQUIRED TO MATCH PRODUCT APPROVALS SUBMITTED.
  