Date Text
2007-08-06 11:27:09*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) THE MECHANICAL PLANS NEED THE JOB ADDRESS ON THEM,
 SEE 2004 FBC, CITY WPB AMEND. 106.1.3.
  
 3) THE MECHANICAL PLANS SHOW THE 12" SUPPLY DUCT GOING
 TO THE RETURN AIR PLENUM, PLEASE CORRECT.
  
 4) MECHANICAL PLANS SHOW TWO EXISTING AIR HANDLER UNITS
 BEING RELOCATED TO THE NEW ADDITION, PLEASE SHOW THE
 SUPPLY AND RETURN AIR DUCTS THAT WILL BE CONNECTED TO
 THE PLENUMS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.