Plan Review Notes
Plan Review Notes For Permit 07070949
Permit Number 07070949
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-06 08:53:48 
 DENIED/INCOMPLETE INFORMATION
  
 1} NOT KNOWING THE SERVICE CALCULATION FOR THE
 RESIDENCE AS IT WAS CALCULATED WITH THE EQUIPMENT
 PRESENT AR THE TIME, AND DUE TO 230.90 EXCEPTION #3,
 WHICH READS AS FOLLOWS:
 "EXCEPTION NO. 3: TWO TO SIX CIRCUIT BREAKERS OR SETS
 OF FUSES SHALL BE PERMITTED AS THE OVERCURRENT DEVICE
 TO PROVIDE THE OVERLOAD PROTECTION. THE SUM OF THE
 RATINGS OF THE CIRCUIT BREAKERS OR FUSES SHALL BE
 PERMITTED TO EXCEED THE AMPACITY OF THE SERVICE
 CONDUCTORS, PROVIDED THE CALCULATED LOAD DOES NOT
 EXCEED THE AMPACITY OF THE SERVICE CONDUCTORS",A LOAD
 CALCULATION FOR THE SERVICE IS REQUIRED TO CONFIRM THE
 SERVICE CONDUCTORS ARE OF ADEQUATE CAPACITY FOR THE
 ADDED LOADS. SEE 220.83, 2005 NEC.
  
 2} THE WATER HEATER ON THE PLAN WAS NOT INCLUDED IN THE
 PANEL SCHEDULE SUBMITTED. ADD TOTHE CALCULATION IF
 THIS EQUIPMENT IS BEING ADDED. SEE ARTICLE 422.13 FOR
 125%. SHOW THE LOCATION OF THEDISCONNECTING MEANS PER
 422.31. ALSO SEE 422.16 REGARDING FLEXIBLE CORDS, THIS
 UNIT WILL MOST LIKELY BE REQUIRED TO BE HARDWIRED.
  
 3} THE LOADS ADDED OIN THE PANEL SCHEDULE , SHEET A-3,
 ARE LABLED FOR A KITCHEN AND FAMILY ROOM,YET THE
 ADDITION SUBMITTED FOR REVIEW CONTAINS A STUDIO AND
 BATHROOM, PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  