2007-08-06 08:53:48 | |
| DENIED/INCOMPLETE INFORMATION |
| |
| 1} NOT KNOWING THE SERVICE CALCULATION FOR THE |
| RESIDENCE AS IT WAS CALCULATED WITH THE EQUIPMENT |
| PRESENT AR THE TIME, AND DUE TO 230.90 EXCEPTION #3, |
| WHICH READS AS FOLLOWS: |
| "EXCEPTION NO. 3: TWO TO SIX CIRCUIT BREAKERS OR SETS |
| OF FUSES SHALL BE PERMITTED AS THE OVERCURRENT DEVICE |
| TO PROVIDE THE OVERLOAD PROTECTION. THE SUM OF THE |
| RATINGS OF THE CIRCUIT BREAKERS OR FUSES SHALL BE |
| PERMITTED TO EXCEED THE AMPACITY OF THE SERVICE |
| CONDUCTORS, PROVIDED THE CALCULATED LOAD DOES NOT |
| EXCEED THE AMPACITY OF THE SERVICE CONDUCTORS",A LOAD |
| CALCULATION FOR THE SERVICE IS REQUIRED TO CONFIRM THE |
| SERVICE CONDUCTORS ARE OF ADEQUATE CAPACITY FOR THE |
| ADDED LOADS. SEE 220.83, 2005 NEC. |
| |
| 2} THE WATER HEATER ON THE PLAN WAS NOT INCLUDED IN THE |
| PANEL SCHEDULE SUBMITTED. ADD TOTHE CALCULATION IF |
| THIS EQUIPMENT IS BEING ADDED. SEE ARTICLE 422.13 FOR |
| 125%. SHOW THE LOCATION OF THEDISCONNECTING MEANS PER |
| 422.31. ALSO SEE 422.16 REGARDING FLEXIBLE CORDS, THIS |
| UNIT WILL MOST LIKELY BE REQUIRED TO BE HARDWIRED. |
| |
| 3} THE LOADS ADDED OIN THE PANEL SCHEDULE , SHEET A-3, |
| ARE LABLED FOR A KITCHEN AND FAMILY ROOM,YET THE |
| ADDITION SUBMITTED FOR REVIEW CONTAINS A STUDIO AND |
| BATHROOM, PLEASE CLARIFY. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |