Date |
Text |
2007-08-23 10:45:21 | SINGLE FAMILY RESIDENCE ADDITION BUILDING REVIEW FIRST |
| CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC 2004 |
| WITH 2006/2007 REVISIONS. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| 2- BRING DRAWINGS TO PALM BEACH COUNTY (2300 N. JOG RD |
| (561)233-5115) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF IMPACT |
| FEES ARE DUE. |
| |
| 3- SHEET G-1: |
| A) TOTAL ROOF BOTTOM CHORD LOADS DON'T ADD UP |
| CORRECTLY. REVISE AS REQUIRED. |
| |
| B) REVISE MASONRY NOTE #1. SEE SEC. R606.4 OF 2004 |
| FLORIDA RESIDENTIAL CODE FOR MINIMUM ALLOWABLE STRESS |
| OF CONCRETE MASONRY UNITS. |
| |
| C) REVISE PLAN NOTE #3.SEE FBC 2004 AND 2004 |
| FLORIDA RESIDENTIAL CODE FOR CORRECT SECTIONS TO BE |
| CITED. |
| |
| D) REVISE PLAN NOTE #7. WHERE IS THE TABLE 2405.3 & |
| .3A REFERENCED IN THIS NOTE?. NONE FOUND IN THE CODE. |
| REVISE AS REQUIRED. |
| |
| E) REVISE FRAMING NOTE #15. SEE ASTM C926 AND ASTM |
| C1063 FOR CORRECT NAIL SIZEAND MINIMUM EMBEDMENT |
| REQUIREDAT HORIZONTAL FRAMING MEMBERS. |
| |
| 4- SPECIFY INSULATION ON WALL SEPARATING GARAGE FROM |
| A/C AREA. SEE ENERGY CALCULATIONS. |
| |
| 5- PROVIDE COMPLETE SPECIFICATIONS FOR SEPARATION OF |
| GARAGE FROM OTHER LIVING AREAS TO SHOW COMPLIANCE WITH |
| SECTION R309 OF 2004 FLORIDA RESIDENTIAL CODE.PROVIDE |
| COMPLETE SPECS FOR DOORAND CEILING CONSTRUCTION. |
| |
| 6- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. |
| IF USINGNAILS OR SCREWS SPECIFY TYPE AND NUMBER. IF |
| USING ADHESIVE SPECIFY TYPE AND PROVIDE PRODUCT |
| APPROVAL AS REQUIRED BY DCA RULE 9B-72. |
| |
| 7- HANDRAIL DETAILS SHOWN ON SHEET A-3 DON'T APPLY TO |
| THIS PROJECT. REVISE AS REQUIRED. PROVIDE COMPLETE |
| DETAILS/SPECS TO SHOW COMPLIANCE WITH SEC. R311.5.6 OF |
| 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 8- PROVIDE DETAILS/SPECS AT STAIRWAY SHOWING COMPLIANCE |
| WITHSEC. R602.1.2(3) OF 2004 FLORIDA RESIDENTIAL CODE |
| REGARDING FIREBLOCKING. |
| |
| 9- PROVIDE COMPLETE ENGINEERING FOR "CHANCE HELICAL |
| PILE-SS150"REQUESTED ON FOUNDATION PLAN. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| 10- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: |
| A) ALL USP AND SIMPSON STRUCTURAL CONNECTORS |
| SPECIFIED ON PLANS AND DETAILS. |
| *** NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND SHEET WHERE CONNECTOR IS TO SAVE PAPER. |
| |
| B) WINDOW MULLIONS. AND, CLEARLY INDICATE FASTENING |
| TO VERIFY COMPLIANCE WITH DESIGN PRESSURES CALCULATED |
| BY THE ARCHITECT. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| |
| 11- ALL PRODUCT APPROVALS TO BE REVIEWED AND APPROVED |
| IN WRITING (NOT SIGNING AND SEALING) BY THE DESIGNER OF |
| RECORD AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO |
| FBC 2004. |
| |
| 12- ENERGY CALCULATIONS: |
| A) REVISE JURISDICTION NUMBER. THIS CITY IS 604700, |
| NOT 601000. |
| |
| B) CLARIFY ITEM 8(B):WHERE IS THE SLAB ON GRADE |
| EDGE INSULATION OF R-11 LOCATED? IDENTIFY ON PLANS. |
| |
| C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| |
| 13- PROVIDE DETAIL/SECTION THRU GARAGE EXTERIOR MASONRY |
| WALL SHOWING INSULATION SHOWN ON ENERGY CALCULATIONS. |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 14- SHEET A-3: THICKNESS OF PLYWOOD ROOF SHEATHING |
| SHOWN ON TYP. 2ND STORY WOOD FRAMED WALLSECTION |
| DOESN'T MATCH SIZE SPECIFIED ON DIAPHRAGM SCHEDULE ON |
| SHEETS-2. REVISE AS REQUIRED. |
| |
| 15- SHEET S-1: |
| A) REVISE ALL STRUCTURAL CONNECTORS USP/SIMPSON |
| SPECIFIED ON FIRST FLOOR AND LOW ROOF FRAMING/BRACING |
| PLAN. NEED TO SPECIFY WOOD TO MASONRY CONNECTORS WHERE |
| REQUIRED.REVISE PLAN AND DETAILSON SHEET S-2 AS |
| REQUIRED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| B) DETAIL 4/S2SHOWN ON FIRST FLOOR FRAMING PLAN |
| DOESN'T WORK.NEED TO SHOW SECOND FLOOR WALL. DETAIL |
| ONLY SHOWS CONNECTION FROM MASONRY WALL TO ROOF TRUSS. |
| REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| C) SECOND FLOOR FRAMING PLAN:NEED TO SPECIFY |
| CONNECTOR AT THE OTHER END OF GIRDER TRUSS FRAMING |
| STAIRWAY OPENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |