Plan Review Notes
Plan Review Notes For Permit 07070946
Permit Number 07070946
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-07 13:21:50 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005
 NEC, AND FOUND NONE COMPLIANT WITH THE FOLLOWING:
  
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION
 FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT .106.5 FBC
 AS AMENDEED.
  
 2} INDICATE COMPLIANCE WITH 600.6 FOR THE DISCONNECTING
 MEANS.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]