Plan Review Notes
Plan Review Notes For Permit 07070946
Permit Number 07070946
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-04 09:48:06SIGN BUILDING REVIEW FIRST CHECKLIST.
 REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- SHEET A-0.1
 A) NEED TO BE SIGNED AND SEALED BY THE ARCHITECT AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 B)ARCHITECT NEEDS TO PROVIDE ALL HIS INFORMATION
 IN THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 2- ENGINEER TO PROVIDE ALL THE WIND LOAD INFORMATION AS
 REQUIRED BY SEC. 1609.1 FBC 2004 AND SPECIFY CODES FOR
 WHICH STRUCTURE WAS DESIGNED.
  
 3- INFORMATION SUBMITTED ON SHEET A-0.1 DOESN'T MATCH
 INFORMATION SUBMITTED BY ENGINEER. REVISE AS REQUIRED
 TO MATCH.
  
 4- PROVIDE CURRENT RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: ALSO, USE REVISED NOTICE OF COMMENCMENT FORM
 AND MAKE SURE CONTRACTOR' SINFORMATION AND COMPLETE
 SCOPE OF WORK IS PROVIDED.
  
 5-A) ENGINEERED DRAWINGS TO PROVIDE COMPLETE SIGN
 FRAMEWORK AND CONSTRUCTION SPECIFICATIONS. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 B) ENGINEERED DRAWINGS TO BE CLEAR COPIES. DRAWINGS
 SUBMITTED ARE NOT LEGIBLE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712