Plan Review Notes For Permit 07070946 |
Permit Number |
07070946 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-04 09:48:06 | SIGN BUILDING REVIEW FIRST CHECKLIST. | | REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- SHEET A-0.1 | | A) NEED TO BE SIGNED AND SEALED BY THE ARCHITECT AS | | REQUIRED BY CHAPTER 481 FLORIDA STATUTE. | | | | B)ARCHITECT NEEDS TO PROVIDE ALL HIS INFORMATION | | IN THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF | | FLORIDA ADMINISTRATIVE CODE. | | | | 2- ENGINEER TO PROVIDE ALL THE WIND LOAD INFORMATION AS | | REQUIRED BY SEC. 1609.1 FBC 2004 AND SPECIFY CODES FOR | | WHICH STRUCTURE WAS DESIGNED. | | | | 3- INFORMATION SUBMITTED ON SHEET A-0.1 DOESN'T MATCH | | INFORMATION SUBMITTED BY ENGINEER. REVISE AS REQUIRED | | TO MATCH. | | | | 4- PROVIDE CURRENT RECORDED NOTICE OF COMMENCEMENT AS | | REQUIRED BY SEC. 713.13 FLORIDA STATUTE. | | ***NOTE: ALSO, USE REVISED NOTICE OF COMMENCMENT FORM | | AND MAKE SURE CONTRACTOR' SINFORMATION AND COMPLETE | | SCOPE OF WORK IS PROVIDED. | | | | 5-A) ENGINEERED DRAWINGS TO PROVIDE COMPLETE SIGN | | FRAMEWORK AND CONSTRUCTION SPECIFICATIONS. SEC. 106.1.2 | | CITY AMENDMENTS TO FBC 2004. | | | | B) ENGINEERED DRAWINGS TO BE CLEAR COPIES. DRAWINGS | | SUBMITTED ARE NOT LEGIBLE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|