Date Text
2007-08-17 15:38:17 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 2} INDICATE COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BLDG CODE.
  
 3} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND LIGHTING. 106.3.5
  
 4} } PROVIDE A PANEL SCHEDULE SO THAT BRANCH/FEEDER
 CIRCUIT CONDUCTOR AND OVER CURRENT PROTECTION
 COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC AS
 AMENDED.
  
 5} PROVIDE EMERGENCY ILLUMINATION PER
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC. INDICATE SAME ON PLANS. LOCATE THE BATTERY
 PACKS AND EXIT LIGHTS ON SHEET E-1 WITH THE LIGHTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  