2007-08-26 14:59:57 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.)PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| |
| |
| 2.)PROVIDE INFORMATION IN REGARDS TO THE EXISTING |
| BUILDING CONSTRUCTION; SPECIFICALLY REGARDING THE |
| TECTUM DECK.IT IS MY UNDERSTANDING THAT TECTUM HAS A |
| CLASS A INTERIOR FINISH CLASSIFICATION AND IS |
| CONSIDERED A NONCOMBUSTIBLE; YOU ARE REPLACING NON |
| COMBUSTIBLE STRUCTURAL ELEMENTS (PERLINS AND ROOF |
| SHEATHING) WITH COMBUSTIBLE.REQUIREMENTS ARE NOT |
| READILY APPARENT AS YOU HAVE NOT PROVIDED ALMOST NO |
| INFORMATION IN REGARDS TO THE EXISTING BUILDING; SEE |
| OTHER COMMENTS. |
| |
| 3.)PROVIDE A SITE PLAN SHOWING BUILDING LOCATION ON |
| THE LOT AND LOCATION OF WORK PROPOSED.INCLUDE |
| APPROXIMATE SQUARE FOOT AREA.FROM THE PLAN, IT |
| APPEARS AS THOUGH THE ENTIRE ROOF DECK IS TO BE |
| REPLACED; IS THIS CORRECT? |
| |
| 4.)DECLARE EITHER LEVEL OF ALTERATION OR DECLARE THIS |
| A "REPAIR" ON THE PLAN, FBC EB CHAPTER 3. |
| |
| 5.)PROVIDE PRODUCT APPROVALS FOR THE ROOF.THE |
| ENGINEERING LETTER FOR ENHANCED FASTENING REFERS TO AN |
| NOA BUT THE EVALUATION REPORT WAS NOT PROVIDED. |
| |
| 6.)PROVIDE CALCULATIONS FOR THE ROOF PRESSURES. |
| |
| 7.)A ROOF PERMIT IS REQUIRED. SUBMIT AN APPLICATION. |
| |
| |