Plan Review Notes
Plan Review Notes For Permit 07070832
Permit Number 07070832
Review Stop B
Sequence Number 6
Notes
Date Text
2008-04-11 15:39:34BUILDING PLAN REVIEW
 PERMIT: 07070832
 ADD: 4455 MEDICAL CENTER WAY
 CONT: GSD CONTRACTING LLC
 TEL: (954)646-3538
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1) THE CREATING A NEW ELECTRICAL CLOSET BY ADDING NEW
 WALLS AND DOORS TO ENCLOSE AN ELECTRICAL PANEL HAS
 CREATED AN ELECTRICAL VIOLATION.THE NEW ELECTRICAL
 ROOM 103B IS NOT DEEP ENOUGH TO HAVE THE CLEAR AREA IN
 FRONT OF THE PANEL, THIS WILL BE COVERED IN THE
 ELECTRICAL REVIEWERS COMMENTS WHEN PLANS ARE SUBMITTED
 UNDER THE "E" SHEETS. CURRENTLY THE ONLY CODE SECTION
 THAT COVERS THIS UNDER THE BUILDING PORTION IS 2701.1.
 SCOPE.
 THIS CHAPTER GOVERNS THE ELECTRICAL COMPONENTS,
 EQUIPMENT AND SYSTEMS USED IN BUILDINGS AND STRUCTURES
 COVERED BY THIS CODE. ELECTRICAL COMPONENTS, EQUIPMENT
 AND SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NFPA 70, NATIONAL
 ELECTRICAL CODE , EXCEPT ARTICLE 80.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved