Date |
Text |
2008-04-11 15:39:34 | BUILDING PLAN REVIEW |
| PERMIT: 07070832 |
| ADD: 4455 MEDICAL CENTER WAY |
| CONT: GSD CONTRACTING LLC |
| TEL: (954)646-3538 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISIONREVIEW |
| ACTION: DENIED |
| |
| 1) THE CREATING A NEW ELECTRICAL CLOSET BY ADDING NEW |
| WALLS AND DOORS TO ENCLOSE AN ELECTRICAL PANEL HAS |
| CREATED AN ELECTRICAL VIOLATION.THE NEW ELECTRICAL |
| ROOM 103B IS NOT DEEP ENOUGH TO HAVE THE CLEAR AREA IN |
| FRONT OF THE PANEL, THIS WILL BE COVERED IN THE |
| ELECTRICAL REVIEWERS COMMENTS WHEN PLANS ARE SUBMITTED |
| UNDER THE "E" SHEETS. CURRENTLY THE ONLY CODE SECTION |
| THAT COVERS THIS UNDER THE BUILDING PORTION IS 2701.1. |
| SCOPE. |
| THIS CHAPTER GOVERNS THE ELECTRICAL COMPONENTS, |
| EQUIPMENT AND SYSTEMS USED IN BUILDINGS AND STRUCTURES |
| COVERED BY THIS CODE. ELECTRICAL COMPONENTS, EQUIPMENT |
| AND SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED IN |
| ACCORDANCE WITH THE PROVISIONS OF THE NFPA 70, NATIONAL |
| ELECTRICAL CODE , EXCEPT ARTICLE 80. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |