Date |
Text |
2007-12-20 06:42:52 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| MUNICIPAL CODES |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| ******FROM PREVIOUS REVIEWS |
| |
| 1. OK |
| 2. OK |
| |
| 3. ST A-104 EQUIPMENT SCHEDULE #36, X-RAY FILM |
| PROCESSOR. AN INTERCEPTOR AND/OR A NEUTRALIZER TANK MAY |
| BE REQUIRED. PLEASE CONTACT RODNEY COMPO, (561) |
| 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS, |
| (561) 822-2284, E-MAIL [email protected]. THEIR FAX |
| NUMBER IS (561) 822-2287. PLEASE SUBMIT A DETERMINATION |
| FROM ENVIRONMENTAL COMPLIANCE INDICATING REQUIREMENTS, |
| IF ANY, FOR FOR AN INTERCEPTOR OR A NEUTRALIZER TANK, |
| OR A WAIVER. MUNICIPAL CODE ARTICLE III SECTION |
| 90-125(B)(1)(2). |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT CONTACT FROM ENVIRONMENTAL |
| COMPLIANCE NOT SUBMITTED. PLEASE CONTACT MR. COMPO OR |
| MR. WILLIAMS FOR A DETERMINATION AS TO THE REQUIREMENT |
| OF AN INTERCEPTOR OR NEUTRALIZER OR NOT. |
| |
| 4. OK |
| |
| 5. SHT A-202 DETAIL 5E. THE GARBAGE DISPOSAL SHALL BE |
| ADA APPROVED. PLEASE SUBMIT THE MANUF. SPECIFICATION |
| SHEETS. GARBAGE DISPOSAL SHALL NOT INTRUDE INTO THE |
| CLEAR FLOOR SPACE REQUIRED FOR THE SINK. |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT NO ADA APPROVAL INDICATED ON |
| GARBAGE DISPOSAL SPECIFICATIONS SHEETS SUBMITTED. |
| |
| 6. OK |
| |
| 7. OK |
| |
| **********NEW COMMENT********** |
| |
| 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN ONLY AS |
| A NOTICE AT THIS TIME. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| ****NO RESPONSE, NOT ADDRESSED BY THE ARCHITECT. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |