2007-11-17 10:24:59 | REVIEW #: 2NE |
| ACTION: PASS/PENDING |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| COMMENTS 1 THROUGH 15 HAVE BEEN ADEQUATELY ADDRESSED |
| AND ARE IN COMPLIANCE. |
| |
| COMMENT 16: THE SAME ENERGY CALCULATIONS FROM PREVIOUS |
| SUBMITTAL HAVE BEEN RESUBMITTED. THE ELECTRICAL |
| DESIGNER IS NOT LISTED ON THE COMPLIANCE FORM. ALSO, |
| THE ROOF TYPE IS NOT CONSISTENT WITH THIS TYPE OF |
| CONSTRUCTION. |
| NOTE: THIS IS A RENOVATION (AS DEFINED IN FBC 13-202) |
| OF PART OF AN EXISTING BUILDING. METHOD A "WHOLE |
| BUILDING COMPLIANCE" IS NOT AVAILABLE AS THIS IS NOT A |
| WHOLE BUILDING CONSTRUCTION PROJECT. METHOD B OR C |
| SHALL BE USED TO SHOW COMPLIANCE IN ACCORDANCE WITH FBC |
| 13-400.0.C.4. |
| METHOD A COMPLIANCE IS ONLY ALLOWED IN EXISTING |
| BUILDINGS IF THE BUILDING CAN NOT BE BROUGHT INTO |
| COMPLIANCE WITH METHOD B OR C PRESCRIPTIVE REQUIREMENTS |
| AND THE ENTIRE BUILDING IS BROUGHT INTO COMPLIANCE WITH |
| METHOD A IN ACCORDANCE WITH FBC 13-101.4.2. |
| PROVIDE CORRECTED ENERGY CALCULATIONS AND RESUBMIT. |
| |
| NOTE: MECHANICAL PLANS HAVE BEEN STAMPED, BUT REVIEW |
| WILL BE IN "FAILED" STATUS PENDING ACCEPTANCE OF ENERGY |
| CALCULATIONS BY ALL INTERESTED TRADES. |
| |