Plan Review Notes
Plan Review Notes For Permit 07070832
Permit Number 07070832
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-11-06 15:49:39*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENLTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 08.PLEASE AMEND OR CLARIFY DISCREPANCIES SHOWN IN THE
 ESCAPE PLAN (SHEET A-000) AS COMPARED TO OTHER PLAN
 SHEETS' EXIT DOORS (I.E. SHEET A-102, E-2). B.DOOR
 145A (A-102) IS SHOWN AS A MEANS OF EGRESS (A-000) BUT
 NOT MARKED AS AN EXIT (E-2). D. DOOR 130B (A-102) IS
 SHOWN AS A MEANS OF EGRESS (A-000) BUT NOT MARKED AS AN
 EXIT (E-2)
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  