Plan Review Notes
Plan Review Notes For Permit 07070832
Permit Number 07070832
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-25 12:53:24 
  
  
  
 *** DENIED2ND REVIEW ***
  
 PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL NEED
 TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH MENTIONED
 THE FOLLOWING CODES WERE BEING REQUESTED ON ELECTRICAL
 PLANS.
 PLEASE SEE ONLY ONE CODE WAS INDICATED.
 PLEASE SEE MISSING NFPA-101 2003
  
 2) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW
 NOTE #2.
 PLEASE SEE THE TITLE BLOCKS ARE MISSING THE REQUIRED
 LICENSE INFORMATION FOR THE ARCHITECTURAL/ENGINEERING
 FIRM PAGE, SOUTHERLAND, PAGE.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND 61G15-23.002 WHICH REQUIRES THE INFORMATION ON
 TITLE BLOCKS. PLEASE SEE FLORIDA STATUTES 471.023 AND
 481.219 WHICH REQUIRES ANY FIRM OFFERING ARCHITECTURAL
 AND ENGINEERING SERVICES TO CONTAIN CERTIFICATE OF
 AUTHORIZATION LICENSE NUMBER FOR SAID FIRM PRACTICING
 UNDER EACH DISCIPLINE.
 PLEASE KNOW THIS COMMENT IS NOT FOR HENZ ENGINEERING AS
 THEIR CA # IS STATE ON TITLE BLOCKS AS REQUIRED.
  
 3) NOTE: PLEASE SEE THE SAME EXACT ENERGY CALCULATIONS
 WERE SUBMITTED BACK.
 PLEASE SEE THAT METHOD *A* MAY NOT BE USED. THIS IS NOT
 A WHOLE BUILDING AS THE METHOD *A* IS FOR.
 THIS IS ALSO A RENOVATION IN AN EXISTING BUILDING WHICH
 MEETS 13-101.1.3, 13-101.2.3.
 PLEASE SEE 13-415.1.B, 13-415.1.C. AND 13-415.2
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS/ENERGY
 CALCULATIONS AND PLEASE BE SURE THESE COORDINATE WITH
 PLANS.
  
 ** PLEASE CLARIFY NOTE #21 ON ELECTRICAL NOTES ON E-3.
 PLEASE SEE FBC CHAPTER 13
  
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  