2007-08-16 11:24:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE CFMS FOR EXISTING EXHAUST DROPS IN AHU 1
 AREA.
  
 2. CHECK AIR BALANCE ON ALL AHU SYSTEMS. AHU 1 AND AHU
 2 WERE CHECKED DURING THIS REVIEW AND WERE FOUND NOT IN
 BALANCE. EXAMPLE: AHU 1 ON SCHEDULE SHOWS 4000 CFM
 SUPPLY (WHICH SEEMS HIGH FOR AN 8 TON SYSTEM) WITH 400
 CFM OF O.A. THE FLOOR PLAN SHOWS 3400 CFM OF SUPPLY
 WITH 2600 CFM OF RETURN. THIS DOES NOT CORRESPOND WITH
 EQUIPMENT SCHEDULE OR BALANCE, EVEN WITH THE 400 CFM OF
 O.A. INCLUDED. EXHAUST COULD NOT BE TAKEN INTO ACCOUNT
 SINCE THE INFORMATION WAS NOT PROVIDED. WHEN ADJUSTING
 BALANCE OF THIS AND ALL SYSTEMS, KEEP IN MIND THAT
 MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT THE
 BUILDING IS PRESSURIZED WITH RESPECT TO THE OUTDOORS
 PER FBC 13-409.1.ABC.2. PROVIDE AN OVERALL AIR BALANCE
 SCHEDULE TO SHOW COMPLIANCE.
  
 3. AHU 2: RETURN AND SUPPLY DROPS IN OFFICE 105 ARE
 REVERSED. PLEASE CORRECT.
  
 4. EXHAUST FANS IN TOILET ROOMS SHALLL EITHER RUN
 CONTINUOUS OR BE INTERLOCKED WITH THE AHU'S TO ASSURE
 THAT AIR SUPPLIED TO THESE SPACES IS EXHAUSTED AND NOT
 RECIRCULATED PER FBC,M 403.2.1(3). PROVISIONS SHALL
 ALSO BE MADE TO ASSURE THAT VENTILATION IS PROVIDED
 DURING PERIODS THAT THE ROOMS OR SPACES ARE OCCUPIED
 PER FBC,M 401.3.
  
 5. AHU 6 SHOWS 1" CONDENSATE FROM UNIT BUT THERE IS A
 NOTE WHICH SAYS THE NEW CONDENSATE IS TO BE 3/4".
 PLEASE CLARIFY.
  
 6. PHYSICAL THERAPY AREA ROOM 145 HAS AN OCCUPANT LOAD
 OF 36 PEOPLE PER TABLE 403.3. AT 15 CFM PER PERSON THE
 TOTAL OUTDOOR AIR REQUIRED IN THIS AREA IS 720 CFM.
 ALSO, NOTE THAT AHU 6, WHICH SERVES THIS AREA, IS NOT
 LISTED ON THE OUTDOOR AIR SCHEDULE. PLEASE CORRECT.
  
 7. ROOM 143 LAUNDRY, DRYER EXHAUST IS REQUIRED AND
 SHALL COMPLY WITH FBC,M SEC. 504. SHOW MEANS, LOCATION
 AND TERMINATION OF THE DRYER EXHAUST DUCT SYSTEM,
 INCLUDING MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 FBC,M 504.1.
  
 8. VERTICAL AHU DETAIL: SHOW MEANS OF SECONDARY OR
 AUXILIARY DRAIN PROTECTION AS REQUIRED BY FBC,M
 307.2.3.
  
 9. AREA SERVED BY AHU 1 CONTAINS A CONFERENCE ROOM
 WHICH HAS A HIGHER OCCUPANT LOAD THAN THE OFFICE AREA.
 THE OUTDOOR AIR REQUIREMENTS FOR THIS AREA SHALL BE
 BASED ON THE SPACE HAVING THE LARGEST OUTDOOR AIR
 REQUIREMENT PER FBC,M 403.3.2. PROVIDE OUTDOOR AIR
 CALCULATIONS TO SHOW COMPLIANCE.
  
 10. THE WAITING/RECEPTION AREA SERVED BY AHU 2 ALSO HAS
 A HIGHER OCCUPANT LOAD THAN THE OFFICE AREAS AND IS
 SUBJECT TO FBC,M 403.3.2. RE-CALCULATE OUTDOOR AIR
 REQUIREMENTS AND SHOW COMPLIANCE WITH THIS SECTION.
 PLEASE ALSO DOUBLE-CHECK REMAINING SYSTEMS FOR
 COMPLIANCE PRIOR TO RESUBMITTAL.
  
 11. AHU-5: FLOOR PLAN ONLY SHOWS 675 CFM OF RETURN.
 PLEASE SHOW HOW BALANCED RETURN IS TO BE ACHIEVED.
 FBC,M 601.4
  
 12. WHIRLPOOL SPA AREA REQUIRES MECHANICAL EXHAUST PER
 FBC,M 402.3.1. THIS AREA MAY NEED TO BE SEPARATED FROM
 OTHER PARTS OF THE PHYSICAL THERAPY AREA AS
 RECIRCULATION OF AIR FROM THE WHIRLPOOL SPA AREA IS
 PROHIBITED PER FBC,M 403.2.1(3).
  
 13. EXHAUST FROM LABS 150 AND 153 HAS A NOTE FOR A
 "WALL CAP" BUT THE DUCT IS NOT SHOWN AS ROUTED TO AN
 EXTERIOR WALL. ALSO, THERE IS NO DETAIL ON M-2 FOR A
 WALL CAP. PLEASE CLARIFY.
  
 14. BOTH OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL
 BE EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT
 WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE.
 VENTILATION OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF
 AUTOMATICALLY SHUTTING OFF DURING PREOCCUPANCY BUILDING
 WARMUP, COOLDOWN, AND SETBACK, EXCEPT WHEN VENTILATION
 REDUCES ENERGY COSTS (E.G., NIGHT PURGE) OR WHEN
 VENTILATION MUST BE SUPPLIED TO MEET CODE REQUIREMENTS.
 GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN
 BUILDING EXHAUST AIR SYSTEMS. GRAVITY (NONMOTORIZED)
 DAMPERS ARE ACCEPTABLE IN SYSTEMS WITH A DESIGN OUTSIDE
 AIR INTAKE OR EXHAUST CAPACITY OF 300 CFM OR LESS. FBC
 13-409.1.ABC.3.3
  
 15. CONDENSER TIE-DOWN DETAIL: THIS DETAIL INDICATES
 CABLES AND STRAPS. WHICH IS TO BE USED? PLEASE CLARIFY.
 IF CABLES OR STRAPS ARE TO BE USED, THEY SHALL NOT
 IMPEDE EQUIPMENT SERVICE ACCESS PER FBC,M 306.1.
  
 16. ENERGY CALCULATIONS:
 A) THE INPUT DATA REPORT SHOWS A METAL BUILDING ROOF W/
 R-19 BATTS. IS THAT AN ACCURATE DESCRIPTION OF THE
 ROOFING SYSTEM USED ON THIS BUILDING?
 B) PLEASE INCLUDE THE PERMIT # ON THE PROJECT SUMMARY
 PAGE.
 C) INCLUDE THE NAME AND REGISTRATION NUMBER OF THE
 ELECTRICAL DESIGNER ON THE CERTIFICATIONS PAGE PER FBC
 13-409.1.ABC.2.
  