Plan Review Notes
Plan Review Notes For Permit 07070832
Permit Number 07070832
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-18 14:36:10*****DENIED*****
  
  
 01.NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 02.INDEX TO DRAWINGS SHOWN ON SHEET A-000 SHOW NO
 REFERENCE TO ELECTRICAL, PLUMBING, OR MECHANICAL
 SHEETS.
  
 03.THE SUITE NUMBER SHALL BE INCLUDED WITH THE
 NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO OR EGRESS FROM THE PROPERTY OR VICINITY
 THEREOF (INCLUDING FIRE LANES).
  
 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENLTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 07.SPECIFY THE INTERIOR FINISH MATERIAL
 CLASSIFICATION FOR THE EXITS, EXIT AISLE CORRIDORS, AND
 ALL OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
 08.PLEASE AMEND OR CLARIFY DISCREPANCIES SHOWN IN THE
 ESCAPE PLAN (SHEET A-000) AS COMPARED TO OTHER PLAN
 SHEETS' EXIT DOORS (I.E. SHEET A-102, E-2).
 A. EXIT DOOR 108A (A-102) NOT SHOWN AS AN EXIT ON
 ESCAPE PLAN (A-000) B.DOOR 145A (A-102) IS SHOWN
 AS A MEANS OF EGRESS (A-100) BUT NOT MARKED AS AN EXIT
 (E-2). C.A MEANS OF EGRESS THROUGH THE WAITING
 AREA #100 (A-000) BUT NO EXIT DOOR IS SHOWN (E-102). D.
 DOOR 130B (A-102) IS SHOWN AS A MEANS OF EGRESS (A-100)
 BUT NOT MARKED AS AN EXIT (E-2)
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  