2007-09-18 14:36:10 | *****DENIED***** |
| |
| |
| 01.NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE |
| PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. |
| |
| 02.INDEX TO DRAWINGS SHOWN ON SHEET A-000 SHOW NO |
| REFERENCE TO ELECTRICAL, PLUMBING, OR MECHANICAL |
| SHEETS. |
| |
| 03.THE SUITE NUMBER SHALL BE INCLUDED WITH THE |
| NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH |
| SUBMITTED PLAN SHEET. |
| |
| 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER |
| ACCESS TO OR EGRESS FROM THE PROPERTY OR VICINITY |
| THEREOF (INCLUDING FIRE LANES). |
| |
| 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| OR MORE FREQUENLTLY AS NECESSARY FOR SAFE OPERATIONS. |
| |
| 07.SPECIFY THE INTERIOR FINISH MATERIAL |
| CLASSIFICATION FOR THE EXITS, EXIT AISLE CORRIDORS, AND |
| ALL OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS |
| C. |
| |
| 08.PLEASE AMEND OR CLARIFY DISCREPANCIES SHOWN IN THE |
| ESCAPE PLAN (SHEET A-000) AS COMPARED TO OTHER PLAN |
| SHEETS' EXIT DOORS (I.E. SHEET A-102, E-2). |
| A. EXIT DOOR 108A (A-102) NOT SHOWN AS AN EXIT ON |
| ESCAPE PLAN (A-000) B.DOOR 145A (A-102) IS SHOWN |
| AS A MEANS OF EGRESS (A-100) BUT NOT MARKED AS AN EXIT |
| (E-2). C.A MEANS OF EGRESS THROUGH THE WAITING |
| AREA #100 (A-000) BUT NO EXIT DOOR IS SHOWN (E-102). D. |
| DOOR 130B (A-102) IS SHOWN AS A MEANS OF EGRESS (A-100) |
| BUT NOT MARKED AS AN EXIT (E-2) |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS |
| ADDRESSED |
| |
| |