 *** DENIED***
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. THE
 ARCHITECTURAL COVE SHEET DOES CONTAIN SOME OF THE CODES
 HOWEVER THE BELOW ARE BEING GIVEN SO THESE MAY BE
 PLACED ON PLANS INCLUSIVE OF A COVER SHEET AND
 E-SHEETS.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED LICENSE INFORMATION FOR THE
 ARCHITECTURAL/ENGINEERING FIRM PAGE, SOUTHERLAND,
 PAGE.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND 61G15-23.002 WHICH REQUIRES THE INFORMATION ON
 TITLE BLOCKS. PLEASE SEE FLORIDA STATUTES 471.023 AND
 481.219 WHICH REQUIRES ANY FIRM OFFERING ARCHITECTURAL
 AND ENGINEERING SERVICES TO CONTAIN CERTIFICATE OF
 AUTHORIZATION LICENSE NUMBER FOR SAID FIRM PRACTICING
 UNDER EACH DISCIPLINE.
 PLEASE KNOW THIS COMMENT IS NOT FOR HENZ ENGINEERING AS
 THEIR CA # IS STATE ON TITLE BLOCKS AS REQUIRED.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE REQUIRED TO COORDINATE WITH THE
 ELECTRICAL PLANS AND LIGHTING AS SHOWN ON PLANS. PLEASE
 SEE THE INPUT DATA REPORT STARTING ON PAGE #2 OF THE
 IDR.
 PLEASE SEE THE TYPE OF FIXTURES, THE NUMBER OF
 FIXTURES, THE WATTAGE AND THE CONTROL METHOD NEEDS TO
 BE COORDINATED WITH PLANS.
 PLEASE SEE THE AMOUNT OF LUMINARIES LISTED ON THE IDR
 INDICATES ONLY ONE FIXTURE FOR EACH TYPE. HOW IS THIS
 POSSIBLE WHEN THERE ARE SEVERAL FIXTURES FOR EACH
 TYPE.
 PLEASE SEE THE METHOD OF CONTROLS ARE SHOWN AS *MANUAL
 ON/OFF* WHEN THE CONTROLS ON PLANS ARE AUTOMATED/TIMERS
 ETC PLEASE CORRELATE.
 PLEASE SEE THE WATTAGE OF THE FIXTURES IS SHOWN 1600,
 1000 WATTS ETC WHEN THE PLANS DO NOT CONTAIN ANY
 FIXTURES OF THIS WATTAGE.
 PLEASE SUBMIT THE TIME OF SCHEDULING FOR SYSTEMS.
 PLEASE INDICATE ALL MAXIMUM TIMES FOR ALL OVER RIDE
 DEVICES, OCCUPANCY TYPE DEVICES ETC.
 PLEASE SEE SOME AREAS OF PLANS SEEM TO BE MISSING
 CONTROLS ARE REQUIRED. (PHYSICAL THERAPY AREA, BUSINESS
 OFFICE AREA)
 13-415.1.ABC.1.1, .1.2, .1.3.
 13-415.1.A, 13-415.2
 PLEASE GO OVER ALL OF THESE ITEMS PER FBC CHAPTER 13
  
 4) NOTE: PLEASE INDICATE NOTES FOR GROUNDING PER 517.13
 (A) AND (B).
 THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE
 CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE
 FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO
 HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES
 THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO
 IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL
 INVOLVED.
 **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS
 IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE
 NOT.
  
 5) NOTE: PLEASE KNOW THE SCOPE OF WORK FOR PHASED
 CONSTRUCTION WILL BE GONE OVER WITH THE INSPECTION
 SERVICES AS MANY AREAS WILL NEED TO BE SAFE AND FULL
 PROTECTION OF ALL SYSTEMS INCLUDING ANY FIRE ALARMS,
 FIRE SPRINKLERS WILL BE REQUIRED TO REMAIN OPERABLE. **
 ONLY BEING NOTED FOR INFORMATION.
  
 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN.
 FBC 106.3.5.1.2
 ** WHERE BUILDINGS CONTAIN A FA SYSTEM**
  
 7) NOTE: PLEASE KNOW ANY LOW VOLTAGE SYSTEMS WIRING
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS.
  
 8) NOTE: PLEASE SEE THE RISER IS SHOWING AN ADDITIONAL
 METER/MAIN FOR ONE OF THE PANELS IN THIS ONE TENANT
 SPACE. THE SINGLE TENANT IS ONLY BEING PERMITTED TO
 CONTAIN ONE METER AND THIS IS A SINGLE OCCUPANCY. THE
 NEW PANEL WHICH IS BEING RELOCATED SHOULD BE FROM THE
 TENANT METER WHICH FEEDS SPACE.
 THIS INFORMATION WILL BE FORWARDED TO ZONING AND
 BUILDING.
 PLEASE SEE LOAD CALCULATIONS FOR SERVICE DOES NOT
 INCLUDE ALL EQUIPMENT MAINS AS SHOWN ON RISER. PLEASE
 SEE MISSING MAIN #3.
 PLEASE COMPLETE AND ADJUST RISER. 90.4 220, 215.3,
 ETC.
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE LS 101 7.8 AND 7.9.
 PLEASE PROVIDE THE MINIMUM LEVELS ARE NEEDED ON THE
 EGRESS PATHS.
 PLEASE SEE FAC 61G15-33.004.
 FBC 106.1.2
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-25 09:58:452007-08-25 09:58:45
  
 REVIEW IN PROGRESS
2007-08-23 21:18:242007-08-23 21:18:24
  
 IN ELEC FOR REVIEW.