2007-08-25 11:46:03 | 2007-08-25 11:46:03 |
| |
| *** DENIED*** |
| |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. THE |
| ARCHITECTURAL COVE SHEET DOES CONTAIN SOME OF THE CODES |
| HOWEVER THE BELOW ARE BEING GIVEN SO THESE MAY BE |
| PLACED ON PLANS INCLUSIVE OF A COVER SHEET AND |
| E-SHEETS. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| NOT MADE BY OTHER TRADE(S). |
| |
| 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE |
| REQUIRED LICENSE INFORMATION FOR THE |
| ARCHITECTURAL/ENGINEERING FIRM PAGE, SOUTHERLAND, |
| PAGE. |
| PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| AND 61G15-23.002 WHICH REQUIRES THE INFORMATION ON |
| TITLE BLOCKS. PLEASE SEE FLORIDA STATUTES 471.023 AND |
| 481.219 WHICH REQUIRES ANY FIRM OFFERING ARCHITECTURAL |
| AND ENGINEERING SERVICES TO CONTAIN CERTIFICATE OF |
| AUTHORIZATION LICENSE NUMBER FOR SAID FIRM PRACTICING |
| UNDER EACH DISCIPLINE. |
| PLEASE KNOW THIS COMMENT IS NOT FOR HENZ ENGINEERING AS |
| THEIR CA # IS STATE ON TITLE BLOCKS AS REQUIRED. |
| |
| 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| SUBMITTED ARE REQUIRED TO COORDINATE WITH THE |
| ELECTRICAL PLANS AND LIGHTING AS SHOWN ON PLANS. PLEASE |
| SEE THE INPUT DATA REPORT STARTING ON PAGE #2 OF THE |
| IDR. |
| PLEASE SEE THE TYPE OF FIXTURES, THE NUMBER OF |
| FIXTURES, THE WATTAGE AND THE CONTROL METHOD NEEDS TO |
| BE COORDINATED WITH PLANS. |
| PLEASE SEE THE AMOUNT OF LUMINARIES LISTED ON THE IDR |
| INDICATES ONLY ONE FIXTURE FOR EACH TYPE. HOW IS THIS |
| POSSIBLE WHEN THERE ARE SEVERAL FIXTURES FOR EACH |
| TYPE. |
| PLEASE SEE THE METHOD OF CONTROLS ARE SHOWN AS *MANUAL |
| ON/OFF* WHEN THE CONTROLS ON PLANS ARE AUTOMATED/TIMERS |
| ETC PLEASE CORRELATE. |
| PLEASE SEE THE WATTAGE OF THE FIXTURES IS SHOWN 1600, |
| 1000 WATTS ETC WHEN THE PLANS DO NOT CONTAIN ANY |
| FIXTURES OF THIS WATTAGE. |
| PLEASE SUBMIT THE TIME OF SCHEDULING FOR SYSTEMS. |
| PLEASE INDICATE ALL MAXIMUM TIMES FOR ALL OVER RIDE |
| DEVICES, OCCUPANCY TYPE DEVICES ETC. |
| PLEASE SEE SOME AREAS OF PLANS SEEM TO BE MISSING |
| CONTROLS ARE REQUIRED. (PHYSICAL THERAPY AREA, BUSINESS |
| OFFICE AREA) |
| 13-415.1.ABC.1.1, .1.2, .1.3. |
| 13-415.1.A, 13-415.2 |
| PLEASE GO OVER ALL OF THESE ITEMS PER FBC CHAPTER 13 |
| |
| 4) NOTE: PLEASE INDICATE NOTES FOR GROUNDING PER 517.13 |
| (A) AND (B). |
| THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE |
| CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE |
| FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO |
| HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES |
| THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO |
| IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL |
| INVOLVED. |
| **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS |
| IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE |
| NOT. |
| |
| 5) NOTE: PLEASE KNOW THE SCOPE OF WORK FOR PHASED |
| CONSTRUCTION WILL BE GONE OVER WITH THE INSPECTION |
| SERVICES AS MANY AREAS WILL NEED TO BE SAFE AND FULL |
| PROTECTION OF ALL SYSTEMS INCLUDING ANY FIRE ALARMS, |
| FIRE SPRINKLERS WILL BE REQUIRED TO REMAIN OPERABLE. ** |
| ONLY BEING NOTED FOR INFORMATION. |
| |
| 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA |
| SHEETS SUBMITTED. |
| ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| REQUIRED ON BASE PLANS AS SHOWN. |
| FBC 106.3.5.1.2 |
| ** WHERE BUILDINGS CONTAIN A FA SYSTEM** |
| |
| 7) NOTE: PLEASE KNOW ANY LOW VOLTAGE SYSTEMS WIRING |
| WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. |
| |
| 8) NOTE: PLEASE SEE THE RISER IS SHOWING AN ADDITIONAL |
| METER/MAIN FOR ONE OF THE PANELS IN THIS ONE TENANT |
| SPACE. THE SINGLE TENANT IS ONLY BEING PERMITTED TO |
| CONTAIN ONE METER AND THIS IS A SINGLE OCCUPANCY. THE |
| NEW PANEL WHICH IS BEING RELOCATED SHOULD BE FROM THE |
| TENANT METER WHICH FEEDS SPACE. |
| THIS INFORMATION WILL BE FORWARDED TO ZONING AND |
| BUILDING. |
| PLEASE SEE LOAD CALCULATIONS FOR SERVICE DOES NOT |
| INCLUDE ALL EQUIPMENT MAINS AS SHOWN ON RISER. PLEASE |
| SEE MISSING MAIN #3. |
| PLEASE COMPLETE AND ADJUST RISER. 90.4 220, 215.3, |
| ETC. |
| FBC 106.3.5.1.2 |
| |
| 9) NOTE: PLEASE SEE LS 101 7.8 AND 7.9. |
| PLEASE PROVIDE THE MINIMUM LEVELS ARE NEEDED ON THE |
| EGRESS PATHS. |
| PLEASE SEE FAC 61G15-33.004. |
| FBC 106.1.2 |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |