Plan Review Notes
Plan Review Notes For Permit 07070832
Permit Number 07070832
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-01 10:57:16BUILDING PLAN REVIEW
 PERMIT: 07070832
 ADD: 4455 MEDICAL CENTER WAY
 CONT: GSD CONTRACTING LLC
 TEL: (954)961-4222
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PAGE SOUTHERN PAGE- ARCHITECTURE INTERIORS
 CONSULTING ENGINEERING
 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 4) SHEET A-000
  
 4A) PLEASE CORRECT THE CODE ANALYSIS, PLANS INDICATE
 THE 2003 IBC.
 FLORIDA USES THE 2004 FBC-BUILDING WITH THE 2006
 REVISIONS.
  
 4B) PLEASE ALSO INCLUDE IN THE CODE ANALYSIS, THE 2004
 FLORIDA EXISTING BUILDING CODE
 WITH 2006 REVISIONS. PLEASE IDENTIFY TO WHAT LEVEL OF
 ALTERATIONS THIS PERMIT WILL COVER UNDER THE SCOPE OF
 WORK.
  
 4C) (2) PLEASE PROVIDE ADDITIONAL INFORMATION SEE TABLE
 503 AS FAR AS IS THE TYPE II BUILDING A TYPE **A OR
 B**.
  
 4D) (5) EGRESS WIDTH PLANS INDICATE 36?, PLEASE SEE
 1016.2 CORRIDOR WIDTH NOT LESS THAN 44 INCHES,
 EXCEPTION 2 STATES THIRTY-SIX INCHES WITH A REQUIRED
 OCCUPANT CAPACITY OF 50 OR LESS.
 OCCUPANT LOAD. THE NUMBER OF PERSONS FOR WHICH THE
 MEANS OF EGRESS OF A BUILDING OR PORTION THEREOF IS
 DESIGNED.
  
 5) SHEET A202 BREAK ROOM SECTION5EISN?T CLEAR AS TO
 CABINET HEIGHT, PLUS THE PLANS INDICATE THE USE OF A
 GARBAGE DISPOSAL, GARBAGE DISPOSAL TO BE ADA APPROVED.
 PLEASE CORRECT, SEE TEXT BELOW IN REGARDS TO BREAK ROOM
 SINK: SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 6) SHEET A102 RESTROOMS 148,150& 153 ARE ALL NEW
 RESTROOMS REQUIRING THE LAV TO BE IN THE RESTROOM.
 11-4.16.2 CLEAR FLOOR SPACE.
 CLEAR FLOOR SPACE FOR WATER CLOSETS NOT IN STALLS SHALL
 COMPLY WITH FIGURE 28. CLEAR FLOOR SPACE MAY BE
 ARRANGED TO ALLOW EITHER A LEFT-HANDED OR RIGHT-HANDED
 APPROACH. NOTE LAVATORIES ARE TO BE PART OF THE TOILET
 ROOM.
  
 7) SHEET A-105 INDICATES ROOM # 137 TO BE USED FOR
 X-RAYS, PLEASE PROVIDE THE FOLLOWING INFORMATION.
 435.5.1 SHIELDING.
 EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY
 PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN
 INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS
 OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64 E-5,
 FLORIDA ADMINISTRATIVE CODE .
  
 435.5.1.1
 STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL
 BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND
 WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET (2.1 M).
  
 435.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED.
  
 435.5.1.3
 PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT
 ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS
 OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF
 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC
 PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH
 FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE
 BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD,
 USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
  
 435.5.1.3.1
 THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING:
 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S
 RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS;
 GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY
 WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S
 BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL.
 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS
 OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS,
 FLOOR AND CEILING OF THE ROOM CONCERNED.
 435.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED.
 435.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT
 AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM
 CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE
 TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS
 MAY BE PRESENT.
 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT
 AND THE MAXIMUM TECHNIQUE FACTORS.
 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS
 WHICH WILL BE PERFORMED WITH THE EQUIPMENT.
  
 8) SHEET E-2 THE PLANS SHOW 2 EXIT DIRECTIONAL LIGHTS
 INDICATING THE EGRESS PATH TRAVELING INTO
 ROOM# 100 WHICH IS A WAITING ROOM WITHOUT A MEANS
 PLEASE CORRECT.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved