Date |
Text |
2007-09-01 10:57:16 | BUILDING PLAN REVIEW |
| PERMIT: 07070832 |
| ADD: 4455 MEDICAL CENTER WAY |
| CONT: GSD CONTRACTING LLC |
| TEL: (954)961-4222 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) PAGE SOUTHERN PAGE- ARCHITECTURE INTERIORS |
| CONSULTING ENGINEERING |
| 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE |
| BLOCK FOR ANY |
| SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER |
| A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| OFFERING ENGINEERING SERVICES, SHALL |
| INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| |
| 4) SHEET A-000 |
| |
| 4A) PLEASE CORRECT THE CODE ANALYSIS, PLANS INDICATE |
| THE 2003 IBC. |
| FLORIDA USES THE 2004 FBC-BUILDING WITH THE 2006 |
| REVISIONS. |
| |
| 4B) PLEASE ALSO INCLUDE IN THE CODE ANALYSIS, THE 2004 |
| FLORIDA EXISTING BUILDING CODE |
| WITH 2006 REVISIONS. PLEASE IDENTIFY TO WHAT LEVEL OF |
| ALTERATIONS THIS PERMIT WILL COVER UNDER THE SCOPE OF |
| WORK. |
| |
| 4C) (2) PLEASE PROVIDE ADDITIONAL INFORMATION SEE TABLE |
| 503 AS FAR AS IS THE TYPE II BUILDING A TYPE **A OR |
| B**. |
| |
| 4D) (5) EGRESS WIDTH PLANS INDICATE 36?, PLEASE SEE |
| 1016.2 CORRIDOR WIDTH NOT LESS THAN 44 INCHES, |
| EXCEPTION 2 STATES THIRTY-SIX INCHES WITH A REQUIRED |
| OCCUPANT CAPACITY OF 50 OR LESS. |
| OCCUPANT LOAD. THE NUMBER OF PERSONS FOR WHICH THE |
| MEANS OF EGRESS OF A BUILDING OR PORTION THEREOF IS |
| DESIGNED. |
| |
| 5) SHEET A202 BREAK ROOM SECTION5EISN?T CLEAR AS TO |
| CABINET HEIGHT, PLUS THE PLANS INDICATE THE USE OF A |
| GARBAGE DISPOSAL, GARBAGE DISPOSAL TO BE ADA APPROVED. |
| PLEASE CORRECT, SEE TEXT BELOW IN REGARDS TO BREAK ROOM |
| SINK: SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE |
| MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE |
| FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH |
| 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH |
| SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| SINK. |
| |
| 6) SHEET A102 RESTROOMS 148,150& 153 ARE ALL NEW |
| RESTROOMS REQUIRING THE LAV TO BE IN THE RESTROOM. |
| 11-4.16.2 CLEAR FLOOR SPACE. |
| CLEAR FLOOR SPACE FOR WATER CLOSETS NOT IN STALLS SHALL |
| COMPLY WITH FIGURE 28. CLEAR FLOOR SPACE MAY BE |
| ARRANGED TO ALLOW EITHER A LEFT-HANDED OR RIGHT-HANDED |
| APPROACH. NOTE LAVATORIES ARE TO BE PART OF THE TOILET |
| ROOM. |
| |
| 7) SHEET A-105 INDICATES ROOM # 137 TO BE USED FOR |
| X-RAYS, PLEASE PROVIDE THE FOLLOWING INFORMATION. |
| 435.5.1 SHIELDING. |
| EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY |
| PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN |
| INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS |
| OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64 E-5, |
| FLORIDA ADMINISTRATIVE CODE . |
| |
| 435.5.1.1 |
| STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL |
| BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND |
| WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7 |
| FEET (2.1 M). |
| |
| 435.5.1.2 |
| DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL |
| HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT |
| REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE |
| INSTALLED. |
| |
| 435.5.1.3 |
| PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT |
| ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS |
| OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF |
| 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC |
| PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH |
| FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE |
| BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, |
| USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR |
| RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN |
| INTO CONSIDERATION. |
| |
| 435.5.1.3.1 |
| THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING: |
| 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S |
| RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS; |
| GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY |
| WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S |
| BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. |
| 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS |
| OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, |
| FLOOR AND CEILING OF THE ROOM CONCERNED. |
| 435.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED. |
| 435.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT |
| AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM |
| CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE |
| TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS |
| MAY BE PRESENT. |
| 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT |
| AND THE MAXIMUM TECHNIQUE FACTORS. |
| 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS |
| WHICH WILL BE PERFORMED WITH THE EQUIPMENT. |
| |
| 8) SHEET E-2 THE PLANS SHOW 2 EXIT DIRECTIONAL LIGHTS |
| INDICATING THE EGRESS PATH TRAVELING INTO |
| ROOM# 100 WHICH IS A WAITING ROOM WITHOUT A MEANS |
| PLEASE CORRECT. |
| |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| |
| |
| |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |