2007-08-30 17:52:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.0SHUTTER CONNECTION MOUNTING TYPE SHOULD BE
 SPECIFIC, SEE SHEET 7 OF THE PANEL PRODUCT APPROVAL.
 YOU'VE CIRCLED 4 BOTTOM, 5 TOP.INCLUDE INFORMATION ON
 YOUR INSTALLATION SCHEDULE.
  
 2.)CONCRETE BLOCK SUBSTRATE FOR THE CONNECTION TYPES
 YOU'VE CIRCLED REQUIRES 3" SPACING.SEE PRODUCT
 APPROVAL, REVISE INSTALLATION SCHEDULE.
  