Plan Review Notes
Plan Review Notes For Permit 07070810
Permit Number 07070810
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-21 11:08:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.THE INSTALLATION SCHEDULE
 SUBMITTED LACKS REQUIRED INFORMATION SUCH AS THE
 SPECIFIC CONNECTION TYPE (SHOULD CORRELATE WITH THE
 ANCHOR SCHEDULE, WILL BE 1 THROUGH 9, TOP OR BOTTOM).
  
 2.AN EDGE DISTANCE OF 2" REQUIRES A .5 FACTOR, SEE
 SHEET 7 (PANELS).
  
 3.)AN EDGE DISTANCE OF 3" REQURES A .86 FACTOR, SEE
 SHEET 11 (ACCORDIONS).
  
 4.)OPENING 3, SPAN OF 38" IS MUCH LESS THAN THE
 OPENING HEIGHT OF 86".FOR A WALL MOUNT, SPAN SHOULD
 BE LARGER THAN OPENING HEIGHT (BLADE LENGTH FOR
 ACCORDIONS).
  
 5.)OPENING 6, YOU STATE THAT HIS IS WORST CASE.YOU
 SPECIFY A SPAN OF 75" FOR A 55" OPENING HEIGHT.
 OPENING 8 HAS AN 84" OPENING HEIGHT, SO HOW IS OPENING
 6 "WORST CASE"?OPENING 4 IS THE SMALLEST OPENING, SO
 THIS OPENING WILL HAVE THE GREATEST DESIGN PRESSURE
 UNLESS THERE ARE OPENINGS IN ZONE 5.
  
 6.)OPENINGS 1 AND 9, PROVIDE THE DIMENSION FOR THE
 DISTANCE TO THE CORNER.ARE ANY OF THESE OPENINGS IN
 ZONE 5?
  
 7.)IT IS ACCEPTABLE TO DESIGN TO "WORST CASE", BUT
 ALL INFORMATION TO DETERMINE CODE COMPLIANCE IS
 REQUIRED.
  