2007-08-21 11:08:16 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| |
| 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| ANOTHER FORMAT, FBC*106.THE INSTALLATION SCHEDULE |
| SUBMITTED LACKS REQUIRED INFORMATION SUCH AS THE |
| SPECIFIC CONNECTION TYPE (SHOULD CORRELATE WITH THE |
| ANCHOR SCHEDULE, WILL BE 1 THROUGH 9, TOP OR BOTTOM). |
| |
| 2.AN EDGE DISTANCE OF 2" REQUIRES A .5 FACTOR, SEE |
| SHEET 7 (PANELS). |
| |
| 3.)AN EDGE DISTANCE OF 3" REQURES A .86 FACTOR, SEE |
| SHEET 11 (ACCORDIONS). |
| |
| 4.)OPENING 3, SPAN OF 38" IS MUCH LESS THAN THE |
| OPENING HEIGHT OF 86".FOR A WALL MOUNT, SPAN SHOULD |
| BE LARGER THAN OPENING HEIGHT (BLADE LENGTH FOR |
| ACCORDIONS). |
| |
| 5.)OPENING 6, YOU STATE THAT HIS IS WORST CASE.YOU |
| SPECIFY A SPAN OF 75" FOR A 55" OPENING HEIGHT. |
| OPENING 8 HAS AN 84" OPENING HEIGHT, SO HOW IS OPENING |
| 6 "WORST CASE"?OPENING 4 IS THE SMALLEST OPENING, SO |
| THIS OPENING WILL HAVE THE GREATEST DESIGN PRESSURE |
| UNLESS THERE ARE OPENINGS IN ZONE 5. |
| |
| 6.)OPENINGS 1 AND 9, PROVIDE THE DIMENSION FOR THE |
| DISTANCE TO THE CORNER.ARE ANY OF THESE OPENINGS IN |
| ZONE 5? |
| |
| 7.)IT IS ACCEPTABLE TO DESIGN TO "WORST CASE", BUT |
| ALL INFORMATION TO DETERMINE CODE COMPLIANCE IS |
| REQUIRED. |
| |